3.13.7 Connecting Ground Cables

Do not connect the ground cable to equipotential connection busbar as shown in 2.
Connect grounded cables to the position labeled 1 in the cabinet or route the PE cable from
the hole at the bottom of the cabinet and connect the cable to the grounded system, as shown
in
Figure
Figure 3-32 Connecting the ground cable

3.13.8 Connecting Outside Water Sensor Cables (Optional)

Connect the outside water sensor based on the site requirements. Perform the following steps:
1.
2.
3.
Figure 3-33
Issue 02 (2013-12-10)
3-32.
Connect the terminals of the water leak cable to the water leak.
Connect the other terminal of the water leak cable to the 13 and 14 ports on X104 as
shown in
Figure
3-23.
Fasten the cable to the unit by coils.
shows the routing cables of water leak sensor.