5.3.3 Power-On

Context
All circuit breakers are set to OFF before delivery. If the preset status has been
changed, restore the preset status before any operation.
Procedure
Step 1 Subsequently switch on main control board power circuit breaker QF8 and general
circuit breaker QF1.
Step 2 Measure the controller loop voltage by using a voltmeter, as shown in
Ensure that the control voltage is within the range of 24 V AC (tolerance ±10%). If
the voltage is not within the range, check whether the voltage jumper matches
the mains, or whether the current input voltage meets normal voltage
requirements.
Issue 17 (2020-10-22)
NO TE
Alarms and LCD buzzer noise may occur if the compressor and fan circuit breakers are not
switched on. The alarms and buzzer noise disappear when the switches are closed.