Monitoring functions
Function not active
Function active
10.4.

Operating time monitoring

Off
Manual
96
On time monitoring M0358
Default value: Function not active
Setting values:
Function <On-time monitoring> deactivated.
Function <On-time monitoring> activated.
Set permissible starts/h
Customer settings M0041
On time monitoring M0355
Permissible starts/h M0357
Default value: 1,200 starts/h
Setting range: 1 ... 1,800 starts/h
Set permissible running time/h
Customer settings M0041
On time monitoring M0355
Perm. running time/h M0356
Default value: 15 min (minutes)
Setting range: 10 ... 60 min (minutes)
This function allows the monitoring of the operating time of the actuator. If the actuator
needs longer than the set time to move from end position OPEN to end position
CLOSED, a warning is signalled (the actuator is not stopped):
Status indication S0005 Warnings
-
Details: Op. time warning
The warning indication is automatically cleared once a new operation command is
executed.
When the actuator moves from an intermediate position to an end position, the set
monitoring time for the whole stroke is assigned in relation to the remaining
stroke/travel.
Operation mode: activate
Required access level: Specialist (4) or higher.
Customer settings M0041
Oper. time monitoring M0568
Operation mode M0569
Default value: Off
Setting values:
The operating time monitoring is switched off
The operating time monitoring is switched on. The permissible operation time is set
via parameter Perm.op. time, manual M0570.
Set permissible operating time manually
Required user level: Specialist (4) or higher.
Customer settings M0041
Oper. time monitoring M0568
Perm.op. time, manual M0570
Default value: 15:00.0 min:s (15 minutes)