Actuator controls
AC 01.2/ACExC 01.2
Signal
Torque wrn OPEN
Torque wrn CLOSE
LPV Sync Out
LPV SA-OPEN
LPV SA-CLOSE
PVST required
FQM FS ready
FQM request
FQM end pos. open
FQM end pos. closed
16.2.

Selection overview of binary signals for digital inputs (DIN)

Table 22:
Signal
Not used
MODE
OPEN
CLOSE
STOP
RESET
I/O interface
OPEN / CLOSE
EMERGENCY
Intermediate pos. 1
Intermediate pos. 2
Intermediate pos. 3
Intermediate pos. 4
Intermediate pos. 5
Intermediate pos. 6
Intermediate pos. 7
Intermediate pos. 8
Intermediate pos. 9
Intermediate pos. 10
Intermediate pos. 11
Intermediate pos. 12
MPV: CW Position 1
MPV: CCW Position 1
MPV: CW Position 2
MPV: CCW Position 2
MPV: CW Position 3
MPV: CCW Position 3
Description
LPV (Lift Plug Valve) synchronisation signal. Master or slave actuator are in an end position.
Operation command in direction OPEN from the master actuator to the slave actuator (SA).
Operation command in direction CLOSE from the master actuator to the slave actuator (SA).
(PVST) Partial Valve Stroke Test should be executed
FQM (fail safe) ready
The fail safe function of the FQM (Fail safe) is active.
FQM has reached end position OPEN at the output drive side.
FQM has reached end position CLOSED at the output drive side.
Depending on the version, the AC is equipped with up to 10 digital inputs.
The inputs are designed for binary signals (standard input level: +24 V DC) and can
be used, for example, to receive operation commands OPEN, STOP, CLOSE, to
control intermediate positions or for the EMERGENCY signal.
Configuration of digital inputs
Required user level: Specialist (4).
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Description
Input not assigned
Change-over between OPEN - CLOSE control and setpoint control
Operation command OPEN
Operation command CLOSE
Operation command STOP
Reset fault signal
Change-over between fieldbus interface and parallel interface
Operation command OPEN/CLOSE for two-wire control
Operation mode for EMERGENCY behaviour
Operation command: Run to intermediate position 1.
Operation command: Run to intermediate position 2.
Operation command: Run to intermediate position 3.
Operation command: Run to intermediate position 4.
Operation command: Run to intermediate position 5.
Operation command: Run to intermediate position 6.
Operation command: Run to intermediate position 7.
Operation command: Run to intermediate position 8.
Operation command: Run to intermediate position 9.
Operation command: Run to intermediate position 10.
Operation command: Run to intermediate position 11.
Operation command: Run to intermediate position 12.
Clockwise approach of position 1
Counterclockwise approach of position 1
Clockwise approach of position 2
Counterclockwise approach of position 2
Clockwise approach of position 3
Counterclockwise approach of position 3
Appendix
135