Output Module - Mitsubishi Electric NZ2GN2S1-32D User Manual

Programmable controller cc-link ie tsn remote i/o module
Hide thumbs Also See for NZ2GN2S1-32D:
Table of Contents

Advertisement

Output module

NZ2GN2S1-32T transistor output module
Item
Station type
Network topology
Number of output points
Rated load voltage
Max. load current
Maximum inrush current
Leakage current at OFF
Max. voltage drop at ON
OFF  ON
Output response time
ON  OFF
Surge suppressor
External power supply for
Voltage
output part
Current
Withstand voltage
Insulation resistance
Noise immunity
Protection degree
Wiring method for common
Protection function
Overload protection
function
Overheat protection
function
External interface
Communication part
Module power supply part
I/O part
Applicable wire size
For power supply
For I/O
Applicable solderless
Terminal block for module
*2
terminal
power supply and FG
Terminal block for output
Cyclic transmission
RX/RY points
RWr/RWw points
Module power supply
Voltage
Current
Weight
*1 Use bar solderless terminals for wiring.
*2 Only one wire can be inserted into a wire insertion opening. Multiple wires cannot be connected to a terminal. Connecting two or more
wires may cause a poor contact.
*3 This value indicates the number of points set by default when the module is dragged and dropped to the network map in the CC IE Field
Configuration window. According to the function used, set an appropriate number of points. ( Page 169 List of remote registers
(output module))
NZ2GN2S1-32T
Intelligent device station
Line topology, star topology, mixture of star topology and line topology, ring topology
32 points
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
0.5A/point, 5A/common
Current is limited by the overload protection function.
0.1mA or less
0.3VDC (TYP.) 0.5A, 0.6VDC (MAX.) 0.5A
0.1ms or less
0.8ms or less (resistive load)
Zener diode
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
40mA or less (TYP. 24VDC per common) External load current is not included.
510VAC for 1 minute between all DC external terminals and ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
IP2X
32 points/common (Common terminal: terminal number 34) (1-wire, spring clamp terminal block
type)
Sink type
Limited current when detecting overcurrent: 1.5 to 3.5A/point
Activated to each point.
Activated to each point.
RJ45 connector
Terminal block for module power supply and FG (2-piece spring clamp terminal block)
2-piece spring clamp terminal block
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.4mm  1.5mm
Stranded wire: 0.3 to 1.5 (22 to 16 AWG)
Page 80 Applicable solderless terminal
Page 88 Applicable solderless terminal
32 points
*3
4 points
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
120mA or less (24VDC, all points ON)
0.18kg
*1
3 SPECIFICATIONS
3.2 Performance Specifications
3
31

Advertisement