Performance Specifications; Input Module - Mitsubishi Electric NZ2GN2S1-32D User Manual

Programmable controller cc-link ie tsn remote i/o module
Hide thumbs Also See for NZ2GN2S1-32D:
Table of Contents

Advertisement

3.2

Performance Specifications

Input module

NZ2GN2S1-32D DC input module
Item
Station type
Network topology
Number of input points
Rated input voltage
Rated input current
Maximum number of simultaneous input points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Input response time
Withstand voltage
Insulation resistance
*2
Noise immunity
Protection degree
Wiring method for common
External interface
Applicable wire size
Applicable solderless
*4
terminal
Cyclic transmission
Module power supply
Weight
*1 If the input response time is set to "0ms", the actual input response time is 80s at OFF  ON, and 160s at ON  OFF.
*2 It is the noise immunity of when the input response time setting value is other than "0ms". Note that the module is easily affected by
noise if "0ms" is set.
*3 Use bar solderless terminals for wiring.
*4 Only one wire can be inserted into a wire insertion opening. Multiple wires cannot be connected to a terminal. Connecting two or more
wires may cause a poor contact.
*5 This value indicates the number of points set by default when the module is dragged and dropped to the network map in the CC IE Field
Configuration window. According to the function used, set an appropriate number of points. ( Page 166 List of remote registers
(input module))
3 SPECIFICATIONS
18
3.2 Performance Specifications
NZ2GN2S1-32D
Intelligent device station
Line topology, star topology, mixture of star topology and line topology, ring topology
32 points
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
6.0mA TYP. (for 24VDC)
100%
11VDC or more/4mA or more
5VDC or less/1.5mA or less
3.3k
OFF  ON
0ms
(Factory default: 1ms)
ON  OFF
510VAC for 1 minute between all DC external terminals and ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
IP2X
32 points/common (Common terminal: terminal number 33, 34) (1-wire, spring clamp terminal block
type)
Positive common/negative common shared type
Communication part
RJ45 connector
Module power supply part
Terminal block for module power supply and FG (2-piece spring clamp terminal block)
I/O part
2-piece spring clamp terminal block
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.4mm  1.5mm
For power supply
For I/O
Stranded wire: 0.3 to 1.5 (22 to 16 AWG)
Page 80 Applicable solderless terminal
Terminal block for module
power supply and FG
Page 88 Applicable solderless terminal
Terminal block for input
RX/RY points
32 points
RWr/RWw points
4 points
Voltage
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current
110mA or less (24VDC, all points ON)
0.20kg
*1
/0.2ms/1ms/1.5ms/5ms/10ms/20ms/70ms
*5
*3

Advertisement

Table of Contents
loading

Table of Contents