Mitsubishi Electric NZ2GN2S1-32D User Manual page 61

Programmable controller cc-link ie tsn remote i/o module
Hide thumbs Also See for NZ2GN2S1-32D:
Table of Contents

Advertisement

*1 If the input response time is set to "0ms", the actual input response time is 80s at OFF  ON, and 160s at ON  OFF.
*2 It is the noise immunity of when the input response time setting value is other than "0ms". Note that the module is easily affected by
noise if "0ms" is set.
*3 Use bar solderless terminals for wiring.
*4 Only one wire can be inserted into a wire insertion opening. Multiple wires cannot be connected to a terminal. Connecting two or more
wires may cause a poor contact.
*5 This value indicates the number of points set by default when the module is dragged and dropped to the network map in the CC IE Field
Configuration window. According to the function used, set an appropriate number of points. ( Page 173 List of remote registers (I/O
combined module))
■External wiring
Terminal block for module
*1
power supply and FG
UNIT POWER
CABLE
1
2
Module power
supply
I/O terminal
*1
block
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Load
22
23
24
25
26
27
28
29
30
31
Load
32
33
34
External power supply for the output
part and load power supply (common)
*1 Only one wire can be inserted into a wire insertion opening. Multiple wires cannot be connected to a terminal. Connecting two or more
wires may cause a poor contact.
Pin
Signal name
No.
1
FG
2
24G
3
+24V
X0
X1
X2
X3
X4
X5
X6
X7
X8
X9
XA
XB
XC
XD
XE
XF
Y10
Y11
Y12
Y13
Y14
Y15
Y16
Y17
Y18
Y19
Y1A
Y1B
Y1C
Y1D
Y1E
Y1F
COM+
COM-
Non-insulated
Constant-
voltage circuit
3 SPECIFICATIONS
3.2 Performance Specifications
3
59

Advertisement

Table of Contents
loading

Table of Contents