Synchronous output timing setting
■Device number
Name
Synchronous output timing setting Y
■Description
When the synchronous timing control mode is used, set the output timing for the synchronization cycle.
Set the timing for when outputs are turned on from off or turned off from on in one synchronization cycle.
For the same output, when Synchronous output timing setting Y OFF to ON (RWw10, RWw12, ... RWw4C, RWw4E) and
Synchronous output timing setting Y ON to OFF (RWw11, RWw13, ... RWw4D, RWw4F) have the same value, output does
not change.
In addition, when a value longer than the synchronization cycle is set, output does not change.
■Setting value
Set the elapsed time after the synchronization cycle timing (unit: 0.1s).
The following table lists the setting values.
Setting value
0 to 65534 (0000H to FFFEH)
65535 (FFFFH)
APPX
186
Appendix 2 Remote Register
Device number
RWw10 to RWw4F
Description
Changes the output at the set timing.
Output does not change.