Appendix 4
The CC-Link IE Field Network processing time (transmission delay time) is structured as follows.
Sequence scan time + link scan time + master station switching time + processing time of slave station = transmission delay
time
Among these, the processing time of slave station is expressed by either of the following.
• Input reflection processing time of intelligent device station (input)
• Output reflection processing time of intelligent device station (output)
The calculation formula for each is as follows.
Input reflection processing time of intelligent device station (input)
Input reflection processing time of intelligent device station (input) = Input response time
*1 If the input response time setting is "0ms", use 0.16ms for calculation.
Output reflection processing time of intelligent device station (output)
Output reflection processing time of intelligent device station (output) = Output response time + internal processing time
(100s)
For the output response time of the I/O module, refer to the following.
Page 31 Output module, Page 46 I/O combined module
CC-Link IE Field Network Processing
Time
*1
+ internal processing time (100s)

Appendix 4 CC-Link IE Field Network Processing Time

A
APPX
193