*1 If the input response time is set to "0ms", the actual input response time is 80s at OFF ON, and 160s at ON OFF.
*2 It is the noise immunity of when the input response time setting value is other than "0ms". Note that the module is easily affected by
noise if "0ms" is set.
*3 Use bar solderless terminals for wiring.
*4 Only one wire can be inserted into a wire insertion opening for the terminal block for module power supply and FG. Multiple wires cannot
be connected to a terminal. Connecting two or more wires may cause a poor contact.
*5 This value indicates the number of points set by default when the module is dragged and dropped to the network map in the CC IE Field
Configuration window. According to the function used, set an appropriate number of points. ( Page 173 List of remote registers (I/O
combined module))
■External wiring
Terminal block for module
power supply and FG
UNIT POWER
CABLE
Module power
supply
I/O terminal
block
Load
Load
External power supply for the output
part and load power supply (common)
*1 Only one wire can be inserted into a wire insertion opening for the terminal block for module power supply and FG. Multiple wires cannot
be connected to a terminal. Connecting two or more wires may cause a poor contact.
3 SPECIFICATIONS
62
3.2 Performance Specifications
*1
Pin
Signal name
No.
1
1
FG
2
2
24G
3
+24V
1
X0
2
X1
3
X2
4
X3
5
X4
6
X5
7
X6
8
X7
9
X8
10
X9
11
XA
12
XB
13
XC
14
XD
15
XE
16
XF
17
Y10
18
Y11
19
Y12
20
Y13
21
Y14
22
Y15
23
Y16
24
Y17
25
Y18
26
Y19
27
Y1A
28
Y1B
29
Y1C
30
Y1D
31
Y1E
32
Y1F
33
COM+
34
COM-
Non-insulated
Constant-
voltage circuit