Function setting switch setting

Set the following functions using the function setting switch on the front of I/O module.
• Network setting function
• Input response time setting function
• Output HOLD/CLEAR setting function
• CC-Link IE Field Network synchronous communication function
• Fast link-up function
The setting of function setting switch is enabled when the I/O module is powered on. Thus, set each function when the module
is powered off.
When operating the function setting switch, use a flathead screwdriver having a blade of 1.2mm or less in
width.
Setting procedure
Set each function with function setting switch 1 to function setting switch 10.
Switch name
Function setting switch 1
Function setting switch 2 to function
setting switch 4
Function setting switch 5
Function setting switch 6
Function setting switch 7
Function setting switch 8
Function setting switch 9
Function setting switch 10
*1 When using the I/O module in CC-Link IE TSN communication mode, refer to the following.
 CC-Link IE TSN Remote I/O Module User's Manual (CC-Link IE TSN Communication Mode)
Do not change any function setting switch while the I/O module is powered on. If the setting of a function
setting switch is changed while the I/O module is powered on, one of the errors from Function setting switch 1
changed error (error code: 0201H) to Function setting switch 10 changed error (error code: 020AH) occurs,
and the changed setting of that function setting switch is not applied. Returning the function setting switch to
its previous position and turning on Error clear request flag (RWw0.b10) eliminate the error.
Function name
NETWORK
Network setting function
RESPONSE
Input response time setting
function
HOLD/CLEAR
Output HOLD/CLEAR setting
function
MODE
CC-Link IE Field Network
synchronous communication
mode setting function
F LINK P1/P2
Fast link-up function
LINK SPEED
Use prohibited
Setting details
• OFF: CC-Link IE TSN communication mode (Factory
*1
default)
• ON: CC-Link IE Field Network communication mode
Set it to ON to perform a unit test. ( Page 141 Unit
Test)
Set the input response time. ( Page 102 Setting
method)
Set output HOLD/CLEAR. ( Page 103 Setting method)
Set the operation mode for the CC-Link IE Field Network
synchronous communication function. ( Page 106
Setting method)
Set the fast link-up function. ( Page 113 Setting
method)
Fix this switch to OFF.
6 INSTALLATION AND WIRING
6.2 Setting Switch
6
75