Error code
Error type
Error name
0205H
Minor error
Function setting switch
5 changed error
0206H
Minor error
Function setting switch
6 changed error
0207H
Minor error
Function setting switch
7 changed error
0208H
Minor error
Function setting switch
8 changed error
0209H
Minor error
Function setting switch
9 changed error
020AH
Minor error
Function setting switch
10 changed error
0220H
Minor error
Error history save limit
error
0240H
Minor error
Module power supply
voltage drop error
0251H
Minor error
Non-volatile memory
access error (error
history)
0260H
Minor error
Remote buffer memory
access error
0261H
Minor error
Incorrect network
parameter access
error
0270H
Minor error
Remote reset disable
error
D0E2H
Communicatio
Station number in use
n error
(own station)
D0E3H
Communicatio
Own station No. out of
n error
range
D217H
Communicatio
Transient data request
n error
command error
D2A0H
Communicatio
Receive buffer full
n error
D2A3H
Communicatio
Transient data length
n error
error
DF01H
Communicatio
Transient data divided
n error
error
Description and cause
Action
The function setting switch 5 has
Return the function setting switch 5 to the setting when the
been changed with the module
module power supply was on.
power supply on.
The function setting switch 6 has
Return the function setting switch 6 to the setting when the
been changed with the module
module power supply was on.
power supply on.
The function setting switch 7 has
Return the function setting switch 7 to the setting when the
been changed with the module
module power supply was on.
power supply on.
The function setting switch 8 has
Return the function setting switch 8 to the setting when the
been changed with the module
module power supply was on.
power supply on.
The function setting switch 9 has
Return the function setting switch 9 to the setting when the
been changed with the module
module power supply was on.
power supply on.
The function setting switch 10
Return the function setting switch 10 to the setting when the
has been changed with the
module power supply was on.
module power supply on.
The upper limit for the number of
No more errors can be saved in the error history. Check the
times an error is saved in the
error by the latest error code.
error history is reached.
The module power supply
voltage is dropped.
The error cannot be saved
because an error in access to the
non-volatile memory was
detected.
An area other than the remote
Correct the setting data of the REMFR/REMTO/REMFRD/
buffer memory areas has been
REMTOD instruction to access the remote buffer memory
accessed using the REMFR/
area range.
REMTO/REMFRD/REMTOD
instruction.
I/O module was accessed when
Set network parameter again correctly.
network parameter was in the
incorrect status.
Remote reset could not be
Return the NETWORK switch to the setting it had when the
performed because the setting of
module was powered on, and then perform remote reset
the NETWORK switch is different
again.
from the setting it had when the
module was powered on.
The setting of the IP address/
Set a unique station number.
station number setting switches
After taking the above action, turn off and on or reset all the
is incorrect.
stations where this error has been detected.
The network parameter is
Add the station information of the module in the network
incorrect or outside the range.
configuration settings of the master station (submaster
station).
The transient data request
Correct the request command at the transient request
command is incorrect.
source, and retry the operation.
The target station is overloaded
and cannot receive transient
data.
The received transient data is
Correct the amount of data (frame length) at the transient
incorrect.
request source, and retry the operation.
Divided transient data has been
Send the transient data that is not divided.
received.
• Check the state of the module power supply.
• Check if the power supply voltage satisfies the
specifications for the I/O module.
• An error that occurred at the time of or before this error
may not be saved into the non-volatile memory.
• Take measures against noise with a shielded cable for
connection.
• If this error occurs again, the possible cause is a module
failure. Please consult your local Mitsubishi representative.
• Check the network status using the CC-Link IE TSN/CC-
Link IE Field diagnostics of the engineering tool, and take
corrective action.
• When the target station is overloaded and cannot receive
transient data, send the data from the send source after
some time has passed.
11 TROUBLESHOOTING