Mitsubishi Electric NZ2GN2S1-32D User Manual page 36

Programmable controller cc-link ie tsn remote i/o module
Hide thumbs Also See for NZ2GN2S1-32D:
Table of Contents

Advertisement

NZ2GN2B1-32T transistor output module
Item
Station type
Network topology
Number of output points
Rated load voltage
Max. load current
Maximum inrush current
Leakage current at OFF
Max. voltage drop at ON
Output response time
Surge suppressor
External power supply for
output part
Withstand voltage
Insulation resistance
Noise immunity
Protection degree
Wiring method for common
Protection function
External interface
Applicable wire size
Applicable solderless
terminal
Cyclic transmission
Module power supply
Weight
*1 Use bar solderless terminals for wiring.
*2 Only one wire can be inserted into a wire insertion opening for the terminal block for module power supply and FG. Multiple wires cannot
be connected to a terminal. Connecting two or more wires may cause a poor contact.
*3 This value indicates the number of points set by default when the module is dragged and dropped to the network map in the CC IE Field
Configuration window. According to the function used, set an appropriate number of points. ( Page 169 List of remote registers
(output module))
3 SPECIFICATIONS
34
3.2 Performance Specifications
NZ2GN2B1-32T
Intelligent device station
Line topology, star topology, mixture of star topology and line topology, ring topology
32 points
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
0.5A/point, 5A/common
Current is limited by the overload protection function.
0.1mA or less
0.3VDC (TYP.) 0.5A, 0.6VDC (MAX.) 0.5A
OFF  ON
0.1ms or less
ON  OFF
0.8ms or less (resistive load)
Zener diode
Voltage
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
Current
40mA or less (TYP. 24VDC per common) External load current is not included.
510VAC for 1 minute between all DC external terminals and ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
IP2X
32 points/common (Common terminal: terminal number 34) (1-wire, screw terminal block type)
Sink type
Overload protection
Limited current when detecting overcurrent: 1.5 to 3.5A/point
function
Activated to each point.
Overheat protection
Activated to each point.
function
Communication part
RJ45 connector
Module power supply part
Terminal block for module power supply and FG (2-piece spring clamp terminal block)
I/O part
34-point two-piece terminal block
Tightening torque range for terminal screw (M3  5.2 screw): 0.43 to 0.57Nm
Tightening torque range for terminal block mounting screw (M3.5 screw): 0.68 to 0.92Nm
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.4mm  1.5mm
For power supply
For I/O
Stranded wire: 0.3 to 2.0 (22 to 14 AWG)
Page 80 Applicable solderless terminal
Terminal block for module
*2
power supply and FG
Terminal block for output
Page 92 Applicable solderless terminal
RX/RY points
32 points
RWr/RWw points
4 points
Voltage
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current
120mA or less (24VDC, all points ON)
0.29kg
*3
*1