Mitsubishi Electric NZ2GN2S1-32D User Manual page 26

Programmable controller cc-link ie tsn remote i/o module
Hide thumbs Also See for NZ2GN2S1-32D:
Table of Contents

Advertisement

NZ2GNCF1-32D DC input module
Item
Station type
Network topology
Number of input points
Rated input voltage
Rated input current
Maximum number of simultaneous input points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Input response time
Withstand voltage
Insulation resistance
*2
Noise immunity
Protection degree
Wiring method for common
External interface
Applicable wire size
Applicable solderless
*4
terminal
Cyclic transmission
Module power supply
Weight
*1 If the input response time is set to "0ms", the actual input response time is 80s at OFF  ON, and 160s at ON  OFF.
*2 It is the noise immunity of when the input response time setting value is other than "0ms". Note that the module is easily affected by
noise if "0ms" is set.
*3 Use bar solderless terminals for wiring.
*4 Only one wire can be inserted into a wire insertion opening for the terminal block for module power supply and FG. Multiple wires cannot
be connected to a terminal. Connecting two or more wires may cause a poor contact.
*5 This value indicates the number of points set by default when the module is dragged and dropped to the network map in the CC IE Field
Configuration window. According to the function used, set an appropriate number of points. ( Page 166 List of remote registers
(input module))
*6 For the points for downward installation, horizontal installation (upside down), and upward installation, refer to the derating chart below.
32
24
Maximum
number of
16
simultaneous
Input voltage
Input voltage
ON points
28.8VDC
8
(points)
26.4VDC
0
0
10
Ambient temperature (­)
3 SPECIFICATIONS
24
3.2 Performance Specifications
NZ2GNCF1-32D
Intelligent device station
Line topology, star topology, mixture of star topology and line topology, ring topology
32 points
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
6.6mA TYP. (for 24VDC)
100%
11VDC or more/4mA or more
5VDC or less/1.5mA or less
3.3k
OFF  ON
0ms
(Factory default: 1ms)
ON  OFF
510VAC for 1 minute between all DC external terminals and ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
IP2X
32 points/common (Common terminal: pin number B1, B2) (1-wire, 40-pin connector type)
Positive common/negative common shared type
Communication part
RJ45 connector
Module power supply part
Terminal block for module power supply and FG (2-piece spring clamp terminal block)
I/O part
40-pin connector
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.4mm  1.5mm
For power supply
For I/O
40-pin connector
The size depends on the connector plug used (sold separately). ( Page 94 Wiring of 40-pin
connector)
Page 80 Applicable solderless terminal
Terminal block for module
power supply and FG
RX/RY points
32 points
RWr/RWw points
4 points
Voltage
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current
110mA or less (24VDC, all points ON)
0.20kg
32 points, 45­
32 points, 55­
28 points, 55­
20
30
40
50 55
*6
*1
/0.2ms/1ms/1.5ms/5ms/10ms/20ms/70ms
*5
*3

Advertisement