Output module

NZ2GNSS2-8TE transistor output module
Item
Station type
Authentication Class
Network topology
Number of output points
Rated load voltage
Maximum load current
Maximum inrush current
Leakage current at OFF
Max. voltage drop at ON
Output circuit response
time
Safety remote station safety cycle time
Communication path response time
Safety remote station refresh response processing
time
Safety remote station output response time
Surge suppressor
External power supply for
*2
output part
Double output type
Withstand voltage
Insulation resistance
Noise immunity
Protection degree
Wiring method for common
Protection function
External interface
Applicable wire size
Applicable solderless
*3
terminal
Multicast filter
Cyclic transmission
*2*4
Module power supply
Safety element
3 SPECIFICATIONS
22
3.2 Performance Specifications
NZ2GNSS2-8TE
Remote station
Authentication Class B
Line topology, star topology, mixture of star topology and line topology, ring topology
Single wiring: 8 points, double wiring: 4 points
24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
0.5A/point, 4A/common
1.0A, 10ms or less
0.1mA or less
0.5VDC (TYP.) 0.5A, 0.8VDC (MAX.) 0.5A
OFFON
0.4ms or less (24VDC)
ONOFF
2.0ms
0.3ms
Safety remote station safety cycle time + Communication path response time
Output circuit response time
Zener diode
Voltage
24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
Current
70mA
Protection function
External power supply overvoltage protection function
Source + Source type
510VAC for 1 minute between all DC external terminals and ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
IP2X
Output 8 points/common (spring clamp terminal block)
Output overload protection function
Communication part
RJ45 connector
Module power supply
Terminal block for module power supply and FG (2-piece spring clamp terminal block (push-in))
part
I/O part, external power
40 points, 2-piece spring clamp terminal block (push-in)
supply part
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.8mm  2.0mm
Terminal block for
module power supply
and FG
I/O terminal block
Stranded wire: 0.5 to 1.5 (20 to 16 AWG)
Terminal block for
Page 44 Applicable solderless terminal
module power supply
and FG
Page 49 Applicable solderless terminal
I/O terminal block
Available
RX/RY points
16 points
RWr/RWw points
4 points
SA\X / SA\Y points
SA\Y: 16 points
Voltage
24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
Current
170mA
Protection function
Module power supply overvoltage protection function, module power supply overcurrent protection
function
Fuse
1.6A (user-unchangeable)
Type B, HFT = 1, SC 3