Xantrex XMP 2600 Programming Manual page 72

Xantrex multiple output power system
Table of Contents

Advertisement

Commands and Queries Reference
RIPL?
ROM?
SEQ
SEQ?
SEQCLR
return the current programmed output ripple for the Power Module.
The result is two decimal numbers: the first being the level (0t o 2)
and the second being the frequency (1 to 7).
Syntax:
Parameters
Category
return a string identifying the XMP 2600. The result is "XMP 2600
x.xx dd/mm/yy" where: x.xx is the firmware revision code and
dd/mm/yy is the firmware date code.
Syntax
Parameters
Category
start / stop sequence program execution.
Syntax
Parameters
Category
return the current state of the Sequence Program. The result is a single
decimal number of value "0" if the program is not running. If the
program is running then the result will have two elements: the first is
the number (1 to 99) of the step being executed and the second is the
amount of time left until the step's operation will be performed
(h:mm:ss).
Syntax
Parameters
Category
clear all Sequence Program Steps (only if program is not running).
Syntax
Parameters
Category
XMP 2600 Programming Manual
RIPL?
none
Settings
ROM?
none
System
SEQ <int>
a value of "0" will stop and a value of "1" will start
the Sequence Program.
System
SEQ?
none
System
SEQCLR
none
System
rev. 1.1
Alphabetical reference
Type: Sequential
Type: Sequential
Type: Sequential
Type: Sequential
Type: Sequential
59