Special Conditions For Safe Use (Iec-Ex Certificate Tun 09.0001 - WAGO -I/O-SYSTEM 750 Manual

2-channel digital output module dc 24 v, shortcircuit protected, high-side switching. 2do 24v dc 2.0a
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-502 2DO 24V DC 2.0A
Po
s: 81.24 /Serie 750 (WAGO-I/O-SYSTEM)/Einsatz in Ex-Bereichen/Besondere Bedingungen für den sicheren Ex-Betrieb gem. IEC-Ex-Zertifikat TUN 09.0001 X @ 7\mod_1274277251185_21.doc @ 56639 @ 3 @ 1
8.2.3
Special conditions for safe use (IEC-Ex Certificate TUN
09.0001 X)
1.
For use as Dc- or Gc-apparatus (in zone 2 or 22) the fieldbus independent
I/O modules WAGO-I/O-SYSTEM 750-*** shall be erected in an enclosure
that fulfils the requirements of the applicable standards (see the marking)
IEC 60079-0, IEC 60079-11, IEC 60079-15, IEC 61241-0 and IEC 61241-1.
For use as group I, electrical apparatus M2, the apparatus shall be erected in
an enclosure that ensures a sufficient protection according to IEC 60079-0
and IEC 60079-1 and the degree of protection IP64. The compliance of
these requirements and the correct installation into an enclosure or a control
cabinet of the devices shall be certified by an ExCB.
2.
Measures have to be taken outside of the device that the rating voltage is not
being exceeded of more than 40% because of transient disturbances.
3.
DIP-switches, binary-switches and potentiometers, connected to the module
may only be actuated when explosive atmosphere can be excluded.
4.
The connecting and disconnecting of the non-intrinsically safe circuits is
only permitted during installation, for maintenance or for repair purposes.
The temporal coincidence of explosion hazardous atmosphere and
installation, maintenance resp. repair purposes shall be excluded.
5.
For the types 750-606, 750-625/000-001, 750-487/003-000, 750-484 the
following shall be considered: The interface circuits shall be limited to
overvoltage category I/II/III (non mains/mains circuits) as defined in IEC
60664-1.
6.
For the type 750-601 the following shall be considered: Do not remove or
replace the fuse when the apparatus is energized.
7.
The ambient temperature range is: 0°C ≤ T
please note certificate).
Po s: 81.25 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1
Manual
Version 1.2.0
Use in Hazardous Environments
≤ +55°C (for extended details