System Description - Output Functions

3.9.5.2 Characteristics

Item
Load voltage to be switched
Switching current
Steady state current
Output contact type
Operate time
Release time
Setting time
Control voltage
(high level)
Control voltage
(low level)
Control current
(high level)

3.9.6 Digital Output Solid State Relay AC

3.9.6.1 Functional Description

The Digital Output Solid State Relay AC (DO-SSR AC) allows the
controller to switch high-voltage AC signals to control solenoids, digital
control valves, alarms, and other loads.
The two output terminals behave as a "volt-free" contact and require an
external AC power supply to drive a load.
FIGURE 3-35 illustrates a simplified block diagram of the DO-SSR AC
self powered connections and FIGURE 3-36 illustrates a simplified
block diagram of the DO-SSR AC externally powered connections.
Fusion4 MSC-L
Installation & Operation Manual
Minimum
Typical
-
-
-
-
-
-
-
SPST
-
-
-
-
-
-
2.5
-
-
-
-
-
Maximum
Unit
265
V
AC
1
A
1
A
-
-
5
ms
10
ms
50
ms
-
V
DC
0.4
V
DC
1
mA
3 - 59