5.15.8.1 Flow Rate
5.15.8.1.1 Initial Flow
Entity
Alarm action
[
]
[Alarm start delay]
[Low percentage]
[High percentage]
5.15.8.1.2 Full Flow
Entity
Alarm action
[
]
[Alarm start delay]
[Low percentage]
[High percentage]
Part No.: 4418309_Rev09
Honeywell
Operation - Arm Configuration
.
Alarms
Description
With this entity you can configure the
alarm behavior, in case this particular
alarm occurs.
With this entity you can configure a
delay after which the MSC-L starts
monitoring the initial flow rate alarm.
With this entity you can configure the
low percentage value for monitoring the
initial flowrate alarm. The initial flowrate
low alarm is raised if the actual flowrate
during the initial flow stage is below the
configured initial flowrate by low
percentage value.
With this entity you can configure the
high percentage value for monitoring
the initial flowrate alarm. The initial
flowrate high alarm is raised if the
actual flowrate during the initial flow
stage is above the configured initial
flowrate by high percentage value.
.
Alarms
Description
With this entity you can configure the
alarm behavior, in case this particular
alarm occurs.
With this entity you can configure a
delay after which the MSC-L starts
monitoring the full flow rate alarm, after
the load profile enters the full flow state.
With this entity you can configure the
low percentage value for monitoring full
flowrate alarm. The full flowrate low
alarm is raised if the actual flowrate
during the full flow stage is below the
configured full flowrate by low
percentage value.
With this entity you can configure the
high percentage value for monitoring
the full flowrate alarm. The full flowrate
high alarm is raised if the actual
flowrate during the full flow stage is
above the configured full flowrate by
high percentage value.
Fusion4 MSC-L
Installation & Operation Manual
Value range
<Disabled>
(default)
<Display>
<Display shutdown>
<Display pause>
<0>
... <255>
s
s
<5>
(default =
s)
<1.0>
... <99.99>
%
%
<5.0> %
(default =
)
<1.0>
... <99.99>
%
%
<5.0>
(default =
%)
Value range
<Disabled>
(default)
<Display >
<Display shutdown>
<Display pause>
<0>
... <255>
s
s
<5> s
(default =
)
<1.0>
... <99.99>
%
%
<5.0>
(default =
%)
<1.0>
... <99.99>
%
%
<5.0>
(default =
%)
5 - 209