Honeywell Fusion4 MSC-L Installation & Operation Manual page 368

Table of Contents

Advertisement

5.14.2.2.2.4 Factored Pulse Output
5.14.2.3 Additive Stream Config. . Stream n . Control Settings
5.14.2.3.1 Additive Control
Entity
[Injection queue length]
[Injection volume]
[Factored pulse out]
5 - 180
Operation - Stream Configuration
This functionality is enabled by defining the
binding.
When the functionality is enabled, the output is driven based on the
transaction additive volume and the factored pulse output setting.
The factored pulse output setting can be one of the following values:
 1 pulse for each unit of additive volume dispensed.
 10 pulses for each unit of additive volume dispensed.
 100 pulses for each unit of additive volume dispensed.
 1000 pulses for each unit of additive volume dispensed.
The unit of volume is defined by the device unit of volume configu-
ration entity and not by the additive volume unit entity.
The maximum frequency of the pulse output channel is 300 Hz.
On the Additive Stream Config . Stream n screen, select
settings>.
The Additive Stream Config . Stream n . Control Settings screen is
displayed with the following entities.
On the Additive Stream Config . Stream n . Control Settings screen,
<Additive
control>.
select
The Additive Stream Config . Stream n . Additive Control screen is
displayed with the following entities.
Description
With this entity you can configure the
inject queue length.
You can define the number of injections
that can be queued up (that is,
postponed) if the injection progress is
too slow in relation to the calculated or
configured injection period time or even
the measured wild stream flow.
With this entity, you can configure the
volume of additive to be dispensed in
each injection.
With this entity you can select the
amount of pulses for each unit of
additive volume dispensed.
Fusion4 MSC-L
Installation & Operation Manual
[Factored pulse out]
Value range
<0> ... <10>
<0>
(default =
)
<0>
<9900>
ml to
ml
<20>
(default =
ml
<1 Pulse / Unit>
(default)
<10 Pulses / Unit>
<100 Pulses / Unit>
<1000 Pulses / Unit>
<1 Pulse / 10 Units>
<1 Pulse / 100 Units>
<1 Pulse / 1000 Units>