Alarm Handling - Operations on alarms
alarms but only moves an alarm from the Asserted state to the
Acknowledged state. This affects only on the alarm indication output.
6.5.5 Resetting all alarms
Resetting all alarms performs a ResetAlarm operation on all currently
active (asserted and acknowledged) alarms.
6.5.6 Acknowledging all alarms
Acknowledging all alarms performs an AcknowledgeAlarm operation on
all currently asserted alarms.
NOTE: The Service Due Reminder alarm has a different
'Reset' operation implemented. In the MSC-L user
interface the Reset button for this alarm is replaced
by an Off button. Press the Off button to switch off
the alarm. Switching off the alarm brings the Alarm
Action temporarily to the Disabled alarm state. When
the system is rebooted or when the alarm is recon-
figured, the Alarm Action is set back to the
configured Alarm Action.
To avoid accidently disabling of this alarm, resetting
all the alarms performs an ordinary reset on the
Service Due Reminder alarm, causing it to become
asserted immediately after again.