Terminal
I/O
CN-141
1
RTD-1
2
RTD-1
3
RTD-1
4
RTD-1
CN-142
1
RTD-2
2
RTD-2
3
RTD-2
4
RTD-2
CN-143
1
RTD-3
2
RTD-3
3
RTD-3
4
RTD-3
CN-144
1
PO-1
2
PO-1
3
PO-2
4
PO-2
4 - 66
Installation - Wiring Termination Guidance
Floor plan
Signal name
ID
S-
RTD S-
C
RTD COM
A
RTD POS
S+
RTD S+
S-
RTD S-
C
RTD COM
A
RTD POS
S+
RTD S+
S-
RTD S-
C
RTD COM
A
RTD POS
S+
RTD S+
HI
Po1_HI
LO
Po1_LO
HI
Po2_HI
LO
Po2_LO
Fusion4 MSC-L
Installation & Operation Manual
Signal
Type
description
Three wire
Resistance
connection
Temperature
Detector input
Neutral
control
Signal - Input
Four wire
connection
Three wire
Resistance
connection
Temperature
Detector input
Neutral
control
Signal - Input
Four wire
connection
Three wire
Resistance
connection
Temperature
Detector input
Neutral
control
Signal - Input
Four wire
connection
Feed
Pulse output
control
Signal - Output
Feed
Signal - Output
Typical
functions
Preferred: PT100
temperature
measurement
according to IEC
60751.
Preferred: PT100
temperature
measurement
according to IEC
60751.
Preferred: PT100
temperature
measurement
according to IEC
60751.
Real time pulse
output, factored
pulse output.
Additive injection
feedback, Alarm
shutdown,
Alarm indication,
Pump start,
Additive blocking
valve