13.2

Offline auto tuning

Magnetic flux
Magnetic flux Sensorless
Magnetic flux
Sensorless
Sensorless
The offline auto tuning enables the optimal operation of a motor.
• Under Advanced magnetic flux vector control or Real sensorless vector control, automatic measurement of motor
constants (offline auto tuning) enables optimal operation of motors even when motor constants vary, when a motor of
another company is used, or when the wiring distance is long.
For the offline auto tuning for a PM motor, refer to
Pr.
Name
71
Applied motor
C100
80
Motor capacity
C101
81
Number of motor
C102
poles
9
Electronic thermal
C103
O/L relay
83
Rated motor voltage
C104
84
Rated motor
C105
frequency
707
Motor inertia
C107
(integer)
724
Motor inertia
C108
(exponent)
96
Auto tuning setting/
C110
status
90
Motor constant (R1) 9999
C120
91
Motor constant (R2) 9999
C121
Motor constant (L1)/
92
d-axis inductance
C122
(Ld)
Motor constant (L2)/
93
q-axis inductance
C123
(Lq)
94
Motor constant (X)
C124
82
Motor excitation
C125
current
Torque current/
859
Rated PM motor
C126
current
Starting resistance
717
tuning
C182
compensation
coefficient 1
Starting resistance
720
tuning
C188
compensation
coefficient
298
Frequency search
A711
gain
page
308.
Initial
Setting range
value
0, 3, 5, 6, 10, 13, 15, 16, 20,
23, 40, 43, 50, 53, 70, 73,
0
8090, 8093, 9090, 9093
0.1 to 30 kW
9999
9999
2, 4, 6, 8, 10, 12
9999
9999
Inverter
rated
0 to 500 A
*2
current
200/400/
0 to 1000 V
*3
575 V
10 to 400 Hz
9999
9999
9999
10 to 999, 9999
9999
0 to 7, 9999
0
1
0
11
*4
0 to 50 Ω, 9999
*4
0 to 50 Ω, 9999
9999
0 to 6000 mH, 9999
9999
0 to 6000 mH, 9999
9999
0% to 100%, 9999
*4
9999
0 to 500 A, 9999
*4
9999
0 to 500 A, 9999
9999
0% to 200%, 9999
9999
0% to 200%, 9999
0 to 32767
9999
9999
By selecting a motor, the thermal characteristic and motor
constant of each motor are set.
*1
Set the applied motor capacity.
V/F control
Set the number of motor poles.
V/F control
Set the rated motor current.
Set the rated motor voltage (V).
Set the rated motor frequency (Hz).
The setting value of Pr.3 Base frequency is used.
Set the motor inertia.
9999: The constant value of Mitsubishi Electric motor (SF-PR,
SF-JR, SF-HR, SF-JRCA, SF-HRCA and so on) is used.
No offline auto tuning
Offline auto tuning is performed without the motor rotating.
Offline auto tuning is performed without the motor rotating
(under V/F control). (Refer to
*4
*4
*4
Tuning data (The value measured by offline auto tuning is
automatically set.)
9999: The constant value of Mitsubishi Electric motor (SF-PR,
SF-JR, SF-HR, SF-JRCA, SF-HRCA and so on) is used.
The offline auto tuning automatically sets the gain required for
the frequency search.
The constant value of Mitsubishi Electric motor (SF-PR, SF-JR,
SF-HR, SF-JRCA, SF-HRCA and so on) is used.
Description
page
358.)
13. (C) Motor Constant Parameters
13.2 Offline auto tuning