• Pr.46 Second torque boost is enabled when the RT signal is ON. To input the RT signal, set "3" in any parameter from
Pr.178 to Pr.189 (Input terminal function selection) to assign the function.
NOTE
• When torque is continuously regenerated as vertical lift load, it is effective to set the rated voltage in Pr.19 Base frequency
voltage to prevent trip due to current at regeneration.
Parameters referred to
Pr.0 Torque
boostpage 374
Pr.178 to Pr.189 (Input terminal function
Pr.14 = 2
For vertical lift loads
At forward rotation boost...Pr.0 setting
At reverse rotation boost...0%
100%
Forward
rotation
Reverse
Pr.0
rotation
Base frequency
Output frequency (Hz)
selection)page 283
Pr.14 = 3
For vertical lift loads
At forward rotation boost...0%
At reverse rotation boost...Pr.0 setting
100%
Reverse
rotation
Forward
Pr.0
rotation
Base frequency
Output frequency (Hz)
379
15. (G) Control Parameters
15.3 Load pattern selection