11. (M) Item and Output Signal for Monitoring
11.6 Output terminal function selection
Signal
Function
name
PID lower limit
PID upper limit
PID forward/reverse
rotation output
Brake opening request
Fan fault output
Heat sink overheat pre-
alarm
Low speed detection
Torque detection
Start time tuning
completion
Trace status
Speed detection
Inverter running 2
Inverter running and start
command ON
During deceleration at
occurrence of power
failure
During PID control
activated
PID deviation limit
During PM sensorless
vector control
During retry
PID output interruption
Safety monitor output
Safety monitor output 2
BACnet binary output
Life alarm
Fault output 3 (Power-
OFF signal)
Operation
Output when the input value is lower than
the lower limit set for the PID control
operation.
Output when the input value is higher than
the upper limit set for the PID control
operation.
Output during forward rotation operation in
the PID control operation.
Output to release the brake while the brake
sequence function is enabled.
Output when a fan fault occurs.
Output when the heat sink temperature rises
to 85% of temperature at which the
protective function of the Heat sink overheat
is activated.
Output when the output frequency drops to
the Pr.865 setting or lower.
Output when the motor torque is higher than
the Pr.864 setting.
Output when the start-time tuning complete. Pr.95, Pr.574
Output during trace operation.
Output when the actual motor rotations per
minute (estimate) reaches the setting of
Pr.42.
Output while the Forward rotation command
signal or Reverse rotation command signal
is ON. Output during deceleration even
while the Forward rotation command signal
or Reverse rotation command signal is OFF
Output while the inverter is running or while
the start command signal is ON.
Output when the power-failure deceleration
function is activated.
(The signal output is retained until the
function stops.)
Output during the PID control operation.
Output when the absolute deviation value
exceeds the limit value.
Output while the operation is performed
under PM sensorless vector control.
Output during retry operation.
Output while PID output suspension function
is activated.
Output while the safety stop function is
activated.
Output when no internal safety circuit failure
exists.
Enables output from the Binary Output
object for BACnet communication. This
signal can be assigned to Pr.192 only. (The
setting is available only for the FR-E800-
EPA.)
Output when the life check function detects
the part approaching the end of its life.
Output when the Fault occurs due to an
inverter circuit fault or connection fault.
Related
Refer to page
parameter
Pr.127 to
Pr.134, Pr.575
329
to Pr.577
Pr.278 to
320
Pr.283, Pr.292
Pr.244
203
Instruction
Manual
(Maintenance)
Pr.865
257
Pr.864
262
315
Pr.1020 to
366
Pr.1047
Pr.42
257
254
254
Pr.261
362
Pr.127 to
Pr.134, Pr.575
329
to Pr.577
Pr.127 to
Pr.134,
329
Pr.553, Pr.554
Pr.71 to Pr.80,
92
Pr.998
Pr.65 to Pr.69
208
Pr.127 to
Pr.134, Pr.575
329
to Pr.577
Instruction
Manual
(Functional
Safety)
Instruction
Pr.549
Manual
(Communication)
Pr.198, Pr.255
to Pr.259,
148
Pr.506,
Pr.507, Pr.509
256

Advertisement