Mitsubishi Electric 800 Series Instruction Manual page 254

Compact, high functionality inverters
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Setting
Signal
Positive
Negative
name
logic
logic
92
192
Y92
93
193
Y93
95
195
Y95
96
196
REM
98
198
LF
99
199
ALM
206
306
Y206
211
311
LUP
212
312
LDN
213
313
Y213
242
342
LNK
9999
*1
Note that changing the frequency setting with an analog signal or the setting dial on the operation panel may cause the turning ON and OFF of
Up to frequency (SU) signal depending on its changing speed and the timing of the speed change determined by the acceleration/deceleration
time setting. (The signal state changing does not occur when the acceleration/deceleration time is set to 0 second.)
NOTE
• One function can be assigned to more than one terminal.
• The function works during the terminal conducts when the parameter setting is any of "0 to 99, 200 to 299", and the function
works during the terminal does not conduct when the setting is "100 to 199, 300 to 399".
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
• Do not assign the signal to terminals A, B, and C which frequently changes its state between ON and OFF. Otherwise, the life
of the relay contact may be shortened.
 Adjusting the output terminal response level (Pr.289)
• The responsivity of the output terminals can be delayed in a range between 5 to 50 ms. (The following is the operation
example of the RUN signal.)
RUN
Pr.289 = 9999
RUN
Pr.289 ≠ 9999
Pr.289
Function
Switches between ON and OFF every time
the average energy saving is updated during
Energy saving average
the energy saving monitoring. This signal
value updated timing
cannot be assigned to any of the relay
output terminal (Pr.192, Pr.320 to Pr.322).
Output in pulses for transmission of the
average current value and the maintenance
Current average monitor
timer value. This signal cannot be assigned
to any of the relay output terminal (Pr.192,
Pr.320 to Pr.322).
Output when the value of Pr.503 reaches
Maintenance timer
the Pr.504 setting or higher.
Output via a terminal by setting a proper
Remote output
number in a relative parameter.
Output when an Alarm fault (fan fault or a
Alarm
communication error) occurs.
Output when the inverter's protective
function is activated to stop the power output
Fault
(when the Fault occurs). The signal output
stops when the inverter reset starts.
Cooling fan operation
Output when the cooling fan operation is
command
commanded.
Upper limit warning
Output when the load fault upper limit
detection
warning is detected.
Lower limit warning
Output when the load fault lower limit
detection
warning is detected.
During load
Output during measurement of the load
characteristics
characteristics.
measurement
Output when the inverter receives a
response from all the slave inverters during
Inverter-to-inverter linkup
initial communication, or when the inverter
returns a response to the master. (Available
for the Ethernet model only.)
No function
OFF
ON
ON
OFF
Pr.289
Operation
Time
11. (M) Item and Output Signal for Monitoring
Related
Refer to page
parameter
Pr.52, Pr.54,
Pr.158, Pr.891
244
to Pr.899
Pr.555 to
153
Pr.557
Pr.503, Pr.504
152
Pr.495 to
263
Pr.497
Pr.121, Pr.244
203
255
Pr.244
203
Pr.1480 to
219
Pr.1492
Instruction
Pr.1124,
Manual
Pr.1125
(Communication)
11.6 Output terminal function selection
11
12
13
14
15
16
17
18
19
20
253

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800

Table of Contents