6.
Displaying analog current (voltage) value
Press the SET key to display the analog current (voltage) value (%) currently applied to terminal 4.
Do not touch the setting dial and UP/DOWN key until calibration is completed.
7.
Applying current (voltage)
Apply a 20 mA (5 V). (Turn the external potentiometer connected between terminals 4 and 5 to a desired position.)
8.
Setting completed
Press the SET key to confirm the setting. The analog current (voltage) value (%) blinks when it is applied.
• Turn the setting dial or press the UP/DOWN key to read another parameter.
• Press the SET key to return to the "C---" display.
• Press the SET key twice to show the next parameter.
280
12. (T) Multi-Function Input Terminal Parameters
12.5 Torque (magnetic flux) setting current (voltage) bias and gain