Mitsubishi Electric 800 Series Instruction Manual page 240

Compact, high functionality inverters
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

2400
1440
1Hz
60Hz
(initial value)
Setting range of Pr.55
• Enter the full-scale value of the meter corresponding to a voltage of 10 VDC output via terminal AM. Enter the current value
(for example, 60 Hz or 120 Hz) at full scale of the meter (10 VDC voltmeter) installed between terminal AM and terminal
5. Output voltage is proportional to the frequency. (The maximum output voltage is 10 VDC.)
Output voltage
10VDC
60Hz
*2
*1
Differs depending on the parameter initial value group. (60/50 Hz)
*2
Output of negative signals enabled when Pr.290 Monitor negative output selection = "1, 5, 9, or 13".
 Current monitor reference (Pr.56)
• Enter the full scale value of a meter used to monitor the output current, the output current peak value, or the motor
excitation current via terminal FM or terminal AM.
• For the FM type inverter, enter the full-scale value of the meter corresponding to a pulse train of 1440 pulses/s output via
terminal FM. Enter the current value at full scale of the meter (1 mA analog meter) installed between terminal FM and
terminal SD. Pulse speed is proportional to the output current monitored. (The maximum pulse train output is 2400 pulses/
s.)
• Enter the full-scale value of the current meter corresponding to a voltage of 10 VDC output via terminal AM. Enter the
current value at full scale of the meter (10 VDC voltmeter) installed between terminal AM and terminal 5. Output voltage is
proportional to the output current monitored. (The maximum output voltage is 10 VDC.)
 Torque monitor reference (Pr.866)
• Enter the full-scale value of the meter used to monitor the output torque via terminal FM or terminal AM.
• For the FM type inverter, enter the full-scale value of the torque meter corresponding to a pulse train of 1440 pulses/s
output via terminal FM. Enter the torque value at full scale of the meter (1 mA analog meter) installed between terminal FM
and terminal SD. Pulse speed is proportional to the torque monitored. (The maximum pulse train output is 2400 pulses/s.)
• Enter the full-scale value of the torque meter corresponding to a voltage of 10 VDC output via terminal AM. Enter the torque
value at full scale of the meter (10 VDC voltmeter) installed between terminal AM and terminal 5. Output voltage is
proportional to the torque monitored. (The maximum output voltage is 10 VDC.)
 Terminal FM pulse train output
• The maximum pulse train output of terminal FM is 8 VDC 2400 pulses/s.
The pulse width can be adjusted on the operation panel by using the calibration parameter C0 FM terminal calibration.
• A 1 mA full-scale DC ammeter or a digital meter can be used to give commands (such as inverter output frequency
command).
Output frequency
590Hz
*1
60Hz
590Hz
(initial value)
Setting range of Pr.55
-10VDC
11. (M) Item and Output Signal for Monitoring
11.3 Monitor display selection for terminals FM and AM
11
12
13
14
15
16
17
18
19
20
239

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800

Table of Contents