Mitsubishi Electric 800 Series Instruction Manual page 156

Compact, high functionality inverters
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

NOTE
• Masking of the data output and sampling of the output current are not performed during acceleration/deceleration.
• If constant speed changes to acceleration or deceleration during start pulse output, it is judged as invalid data, and HIGH
output in 3.5 seconds intervals is performed for the start pulse and LOW output in 16.5 seconds intervals is performed for the
end signal. After the start pulse output is completed, minimum 1-cycle signal output is performed even if acceleration/
deceleration is performed.
Previous cycle
Y93
signal
Start pulse
Output as high pulse shape for 3.5 s
• If the output current value (inverter output current monitor) is 0 A at the completion of the 1-cycle signal output, no signal is
output until the next constant-speed state.
• Under the following conditions, the Y93 signal is output with LOW output in 20 seconds intervals (no data output).
-
When acceleration or deceleration is operating at the completion of the 1-cycle signal output
-
When automatic restart after instantaneous power failure (Pr.57 Restart coasting time ≠ "9999") is set, and the 1-
cycle signal output is completed during the restart operation.
-
When automatic restart after instantaneous power failure (Pr.57 ≠ "9999") is set, and the restart operation was being
performed at the completion of data output masking.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.57 Restart coasting
timepage
Pr.190 to Pr.196 (Output terminal function
Pr.503 Maintenance
timerpage 152
The speed is changed to deceleration from
Output frequency
the constant speed during start pulse output
Invalid cycle (20 s)
351,
page 356
selection)page 250
Time
Next cycle
End signal
Output as low pulse shape for 16.5 s
7. (E) Environment Setting Parameters
7.15 Current average value monitor signal
1
2
3
4
5
6
7
8
9
10
155