Setting Procedure Of Real Sensorless Vector Control (Speed Control) - Mitsubishi Electric 800 Series Instruction Manual

Compact, high functionality inverters
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

5.1
Setting procedure of Real sensorless vector
control (speed control)
Sensorless
Sensorless
Sensorless
Operating procedure
1.
Perform wiring properly. (Refer to the Instruction Manual (Connection).)
2.
Set the applied motor (Pr.71). (Refer to
Set Pr.71 Applied motor to "0" (standard motor) or "10" (constant-torque motor).
3.
Set the overheat protection of the motor (Pr.9). (Refer to
4.
Set the motor capacity and number of motor poles (Pr.80, Pr.81). (Refer to
Operation does not start when the setting value is "9999" (initial value).
5.
Set the rated motor voltage and the rated motor frequency (Pr.83, Pr.84). (Refer to
6.
Select the control method (Pr.800). (Refer to
Select Pr.800 = "10" (speed control) or "12" (speed/torque switchover) to enable speed control.
7.
Set the operation command. (Refer to
Select the start command and speed command.
8.
Set the torque limit (Pr.810). (Refer to
9.
Perform the offline auto tuning (Pr.96). (Refer to
10.
Perform the test operation.
As required
• Select online auto tuning (Pr.95). (Refer to
• Adjust the speed control gain manually. (Refer to
NOTE
• During Real sensorless vector control, offline auto tuning must be performed properly before starting operations.
• The speed command setting range under Real sensorless vector control is 0 to 400 Hz.
• The carrier frequency is limited during Real sensorless vector control. (Refer to
• Torque control is not available in a low-speed (about 10 Hz or lower) regenerative range, or with a low speed and light load
(about 5 Hz or lower and rated torque about 20% or lower).
• This product with the start command ON may also rotate the motor at a low speed when the speed limit value is set to zero.
Confirm that the motor running does not cause any safety problems.
• Switching between the forward rotation command (STF) and reverse rotation command (STR) must not be performed during
operations under torque control. An overcurrent trip (E.OC[]) or opposite rotation deceleration fault (E.11) will occur.
• In case of starting the motor while the motor is coasting under Real sensorless vector control, the frequency search must be
set for the automatic restart after instantaneous power failure function (Pr.57 ≠ "9999", Pr.162 = "10"). (Refer to
• When Real sensorless vector control is applied, there may not be enough torque provided in the ultra low-speed range of about
2 Hz or lower.
Generally, the speed control range is as follows.
For power driving, 1:200 (2, 4 or 6 poles) (available at 0.3 Hz or higher when the rating is 60 Hz), 1:30 (8 or 10 poles) (available
at 2 Hz or higher when the rating is 60 Hz).
For regenerative driving, 1:12 (2 to 10 poles) (available at 5 Hz or higher when the rating is 60 Hz).
98
5. Speed control

5.1 Setting procedure of Real sensorless vector control (speed control)

page
294.)
page
198.)
page
86.)
page
174.)
page
100.)
page
299.)
page
315.)
page
107.)
page
86.)
page
299.)
page
146.)
page
351.)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800

Table of Contents