5.3

Setting the torque limit level

PM
PM
PM
Sensorless
Sensorless
Sensorless
Limit the output torque not to exceed the specified value.
The torque limit level can be set in a range of 0% to 400%. The TL signal can be used to switch between two types of torque
limit.
The torque limit level can be selected by setting it with a parameter, or by using the analog input terminal (terminal 4). Also, the
torque limit levels of forward rotation (power driving/regenerative driving) and reverse rotation (power driving/regenerative
driving) can be set individually.
Pr.
Name
22
Stall prevention operation
H500
level (Torque limit level)
157
OL signal output timer
M430
801
Output limit level
H704
Constant output range
803
torque characteristic
G210
selection
804
Torque command source
D400
selection
805
Torque command value
D401
(RAM)
806
Torque command value
D402
(RAM, EEPROM)
810
Torque limit input method
H700
selection
811
Set resolution switchover
D030
812
Torque limit level
H701
(regeneration)
813
Torque limit level (3rd
H702
quadrant)
814
Torque limit level (4th
H703
quadrant)
815
Torque limit level 2
H710
100
5. Speed control
5.3 Setting the torque limit level
Setting
Initial value
range
*1
0% to 400%
150% / 200%
0 to 25 s
0 s
9999
0% to 400%
9999
9999
0
1
0
2
10
0
1
3
0
4
5
6
600% to
1000%
1400%
600% to
1000%
1400%
0
1
0
2
0
0
10
0% to 400%
9999
9999
0% to 400%
9999
9999
0% to 400%
9999
9999
0% to 400%
9999
9999
Description
Set the torque limit level as a percentage with regards to the rated
torque as 100%.
Set the OL signal output start time at the activation of torque limit
operation.
No OL signal output.
Set the torque current limit level.
The torque limit setting value is used for limiting the torque current
level.
The torque rises in the low-
speed range.
The torque is kept constant in
the low-speed range.
The torque is kept constant in
the low-speed range. (The
torque current is limited.)
The torque is kept constant in
the low-speed range.
Torque command given by analog input via terminal 4
Torque limit by the parameter setting (Pr.805 or Pr.806)
(-400% to 400%)
Torque limit via communication
The internal torque limit 2 cannot be used
Torque limit via communication
Writes the torque limit value in RAM. Regards 1000% as 0%, and
set torque command by an offset of 1000%.
Writes the torque limit value in RAM and EEPROM.
Regards 1000% as 0%, and set torque command by an offset of
1000%.
Internal torque limit 1 (torque limited by parameter settings)
External torque limit (torque limited by terminal 4)
Internal torque limit 2 (torque limited via communication)
Torque limit setting increments 0.1%
Torque limit setting increments 0.01%
Set the torque limit level for forward rotation regenerative driving.
Limit using Pr.22 or the analog terminal values.
Set the torque limit level for reverse rotation power driving.
Limit using Pr.22 or the analog terminal values.
Set the torque limit level for reverse rotation regenerative driving.
Limit using Pr.22 or the analog terminal values.
When the torque limit selection (TL) signal is ON, Pr.815 is the
torque limit value regardless of Pr.810.
The torque limit set to Pr.810 is valid.
The motor power output is
limited to be constant in the
constant power range.
The torque is limited to be
constant in the constant power
range.
The torque is limited to be
constant in the constant power
range unless the output limit of
the torque current is reached.
(The torque current is limited.)
The motor power output is
limited to be constant in the
constant power range.
*2
*2
*2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800

Table of Contents