7.7

Parameter write selection

Whether to enable the parameter write or not can be selected. Use this function to prevent parameter values from being
rewritten by misoperation.
Pr.
Name
77
Parameter write selection
E400
• Pr.77 can be set at any time regardless of the operation mode or operation status. (Setting through communication is
unavailable.)
 Parameter write enabled only during stop (Pr.77 = "0" (initial value))
• Parameters can be written only during a stop in the PU operation mode.
• The following parameters can always be written regardless of the operation mode or operation status.
Pr.
(Multi-speed setting high-speed, middle-speed,
4 to 6
low-speed)
22
Stall prevention operation level
24 to 27
(Multi-speed setting speed 4 to speed 7)
52
Operation panel main monitor selection
54
FM terminal function selection
55
Frequency monitoring reference
56
Current monitoring reference
*1
PWM frequency selection
72
Reset selection/Disconnected PU detection/PU
75
stop selection
77
Parameter write selection
*2
Operation mode selection
79
129
PID proportional band
130
PID integral time
133
PID action set point
134
PID differential time
158
AM terminal function selection
160
User group read selection
232 to 239
(Multi-speed setting speed 8 to speed 15)
*1
Soft-PWM operation selection
240
241
Analog input display unit switchover
268
Monitor decimal digits selection
Stop-on contact excitation current low-speed
*1
275
scaling factor
290
Monitor negative output selection
295
Frequency change increment amount setting
296, 297
(Password setting)
306
Analog output signal selection
310
Analog meter voltage output selection
*2
Communication startup mode selection
340
416, 417
(PLC)
442 to 445
(Ethernet communication)
496, 497
(Remote output)
498
PLC function flash memory clear
*1
Writing during operation is enabled in PU operation mode, but disabled in External operation mode.
*2
Writing during operation is disabled. To change the parameter setting value, stop the operation.
Initial value
Setting range
0
1
0
2
Name
Parameter write is enabled only during stop.
Parameter writing is disabled.
Parameter writing is enabled in any operation mode
regardless of the operation status.
Pr.
*2
NET mode operation command source selection
550
*2
PU mode operation command source selection
551
555 to 557
(Current average value monitoring)
675
User parameter auto storage function selection
774 to 776
(Operation panel monitor item selection)
805
Torque command value (RAM)
806
Torque command value (RAM, EEPROM)
866
Torque monitoring reference
888, 889
(Free parameter)
891 to 899
(Energy saving monitoring)
C0 (900)
FM terminal calibration
C1 (901)
AM terminal calibration
Operation panel setting dial push monitor
992
selection
997
Fault initiation
*2
PM parameter initialization
998
*2
Automatic parameter setting
999
1006
Clock (year)
1007
Clock (month, day)
1008
Clock (hour, minute)
1020
Trace operation selection
1124
Station number in inverter-to-inverter link
1125
Number of inverters in inverter-to-inverter link
system
1150 to 1199
(PLC function user parameters)
1399, 1424 to
1432, 1434 to
(Ethernet communication)
1457
1480 to 1485
(Load characteristics fault)
7. (E) Environment Setting Parameters
Description
Name
7.7 Parameter write selection
1
2
3
4
5
6
7
8
9
10
135

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800

Table of Contents