Mitsubishi Electric 800 Series Instruction Manual page 193

Compact, high functionality inverters
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

NOTE
• The communication interface selection is determined by the setting of Pr.550 and Pr.551.
• The settings of Pr.338 and Pr.339 can be changed during operation when Pr.77 = "2". Note that the changed setting is applied
after the inverter has stopped. Until the inverter has stopped, the previous setting of the interface for the operation command
and the speed command in the Network operation mode is valid.
 Changing the command interface using a signal input via external
terminal (X67 signal)
• In the Network operation mode, the command interface for the operation command and the speed command can be
changed using the Command source switchover (X67) signal. This method may be useful to use both external terminal
and communication interface by using a different interface according to the command type.
• For the X67 signal, set "67" to any parameter from Pr.178 to Pr.184 (Input terminal function selection) to assign the
function to a control terminal.
• When the X67 signal is OFF, the command interface for the operation command and the speed command is the control
terminal.
X67 signal state
Signal not assigned
ON
OFF
NOTE
• The ON/OFF state of the X67 signal is applied only during a stop. When the terminals are switched during operation, the ON/
OFF state is reflected after a stop.
• When the X67 is OFF, a reset via communication is disabled.
• Changing the terminal assignment using Pr.178 to Pr.184 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.59 Remote function
selectionpage 165
Pr.79 Operation mode
selectionpage 174
192
9. (D) Operation Command and Frequency Command
9.3 Start command source and frequency command source during communication operation
Interface for the operation command
Determined by Pr.338 setting
Control terminal only
Interface for the speed command
Determined by Pr.339 setting

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800

Table of Contents