Parameters Related To Bacnet/Ip - Mitsubishi Electric 800 Series Instruction Manual

Communication
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

2.8.3

Parameters related to BACnet/IP

The following parameters are used for BACnet/IP communication. Set the parameters as required.
Pr.
Name
390
% setting reference
N054
frequency
728
Device instance number
N052
(Upper 3 digits)
729
Device instance number
N053
(Lower 4 digits)
1426
Link speed and duplex
*1
mode selection
N641
1442
Ethernet IP filter address 1
*1
N660
1443
Ethernet IP filter address 2
*1
N661
1444
Ethernet IP filter address 3
*1
N662
1445
Ethernet IP filter address 4
*1
N663
1446
Ethernet IP filter address 2
*1
range specification
N664
1447
Ethernet IP filter address 3
*1
range specification
N665
1448
Ethernet IP filter address 4
*1
range specification
N666
*1
The setting is applied after an inverter reset or next power-ON.
 Parameters for monitoring (Pr.52, Pr.774 to Pr.776, Pr.992, and Pr.1027 to
Pr.1034)
• The following items related to BACnet/IP can be monitored.
Parameter setting for monitor item
83
*1
When the count exceeds "9999", the monitor value is reset to "0".
NOTE
• For the description of other settings, refer to the FR-E800 Instruction Manual (Function).
 % setting reference frequency (Pr.390)
• Set a reference frequency of the set frequency. The setting value of Pr.390 % setting reference frequency is 100%
reference. The reference to the frequency command is converted to the set frequency in the following formula.
Set frequency = % setting reference frequency × Speed scale (Refer to
Pr.390 % setting reference frequency
Set frequency written to the inverter
Initial
Setting range
value
60 Hz
1 to 590 Hz
0 to 419
0
(0 to 418)
0 to 9999
0
(0 to 4302)
0
0 to 4
0
0
0 to 255
0
0
9999
9999
0 to 255, 9999
9999
BACnet valid APDU counter (The count of valid APDU detection is displayed.)
0.00 Hz
0%
100.00%
Set frequency (Speed scale)
Description
Set a reference frequency of the set frequency.
Device identifier
When the figure obtained by combining the Pr.728 and Pr.729
settings is not within "0 to 4194302", the setting is out of range.
(The setting range of Pr.729 is "0 to 4302" when Pr.728 = "419".
The setting range of Pr.728 is "0 to 418" when Pr.729 = "4303" or
more.)
Set the communication speed and the communication mode (full-
duplex/half-duplex).
Set the range of connectable IP addresses for the network devices.
(When Pr.1442 to Pr.1445 = "0 (initial value)", the function is
invalid.)
Description
page
74.)
*1
71
2. Ethernet Communication
2.8 BACnet/IP
1
2
3
4
5
6
7
8
9
10