Mitsubishi Electric 800 Series Instruction Manual page 53

Communication
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 Torque command / torque limit using the CC-Link IE Field Network Basic
Torque commands can be given or the torque can be limited by CC-Link IE Field Network Basic communication under Real
sensorless vector control or PM sensorless vector control. The value is used to limit the torque during speed control, and to
give a torque command during torque control. To limit the torque, set Pr.810 Torque limit input method selection = "2". The
torque command / torque limit setting method can be selected using Pr.804 Torque command source selection. (Torque
control cannot be performed with a PM motor.)
Pr.
Name
Torque command source
804
selection
Torque limit input method
810
selection
*1
The torque limit value can also be set using the operation panel.
*2
When a negative value is set as the torque limit, the torque is limited by the absolute value.
 List of I/O devices whose function is changed according to the parameter settings and the
control method
Pr.544 setting
I/O device
RYD
RYE
RXD
RXE
0, 1, 12
RWw1
14, 18
0, 1, 12
RWwC
14, 18
*1
Set Pr.804 = "3 or 5".
*2
Set Pr.810 = "2".
*3
Torque control cannot be performed with a PM motor.
52
2. Ethernet Communication
2.6 CC-Link IE Field Network Basic
Initial
Setting
value
range
0
Torque command given by analog input via terminal 4
Torque command / torque limit using the CC-Link IE Field Network Basic
• Torque command / torque limit (-400% to 400%) by the parameter setting
1
(Pr.805 or Pr.806)
Torque command / torque limit using the CC-Link IE Field Network Basic
• Torque command / torque limit (-400% to 400%) by the parameter setting
3
(Pr.805 or Pr.806)
• Setting is available using the remote register RWw1 or RWwC (-400% to
400%).
0
4
Torque command given by 16-bit digital input (FR-A8AX)
Torque command / torque limit using the CC-Link IE Field Network Basic
• Torque command / torque limit (-327.68% to 327.67%) by the parameter
setting (Pr.805 or Pr.806)
5
(-327.68% to 327.67%)
• Setting is available using the remote register RWw1 or RWwC (-327.68% to
327.67%).
Torque command / torque limit using the CC-Link IE Field Network Basic
• Torque command / torque limit (-327.68% to 327.67%) by the parameter
6
setting (Pr.805 or Pr.806)
0
Internal torque limit (torque limited by parameter settings)
0
1
External torque limit (torque limited by terminal 4)
2
Internal torque limit 2 (torque limited by CC-Link IE Field Network Basic)
V/F control / Advanced magnetic
flux vector control
Frequency setting command (RAM)
Frequency setting command (RAM,
EEPROM)
Frequency setting completion (RAM)
Frequency setting completion (RAM,
EEPROM)
Set frequency
Description
*1*2
*1*2
*2
*1*2
*2
*1*2
Real sensorless vector control / PM sensorless vector
Speed control
Frequency setting / torque limit
command (RAM)
Frequency setting / torque limit
command (RAM, EEPROM)
Frequency setting / torque limit
completion (RAM)
Frequency setting / torque limit
completion (RAM, EEPROM)
Set frequency
*1*2
Torque limit
control
*3
Torque control
Torque command (RAM)
Torque command (RAM,
EEPROM)
Torque command completion
(RAM)
Torque command completion
(RAM, EEPROM)
*1
Torque command
*1
Torque command