Mitsubishi Electric 800 Series Instruction Manual page 46

Communication
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 Input signals (from the inverter to the master module)
Input signals to the master module are as follows. (Output signals from the inverter)
Device No.
RX0
Forward running
RX1
Reverse running
RX2
Running (terminal RUN function)
RX3
Up to frequency
RX4
Overload warning
RX5
— (terminal NET Y1 function)
Frequency detection (terminal FU
RX6
*1
function)
RX7
Fault (terminal ABC function)
RX8
— (terminal NET Y2 function)
RX9
— (DO0 function)
RXA
— (DO1 function)
RXB
— (DO2 function)
RXC
Monitoring
Frequency setting / torque command
RXD
completed (RAM)
Frequency setting / torque command
RXE
completed (RAM, EEPROM)
RXF
Instruction code execution completed
RX16
— (terminal NET Y3 function)
RX17
— (terminal NET Y4 function)
RX1A
Error status flag
RX1B
Remote station ready
*1
These signals are set in the initial setting. Using Pr.190 to Pr.192, output signals assigned to the device numbers can be changed.
For details of Pr.190 to Pr.192, refer to the FR-E800 Instruction Manual (Function).
*2
The signals are fixed. They cannot be changed using parameters.
*3
No signal is assigned in the initial setting. Use Pr.313 to Pr.315 to assign signals to RX9 to RXB.
For details, refer to the description of Pr.190 to Pr.196 (Output terminal function selection) in the FR-E800 Instruction Manual (Function).
*4
No signal is assigned in the initial setting. Use Pr.193 to Pr.196 to assign signals to RX5, RX8, RX16, and RX17.
For details, refer to the description of Pr.193 to Pr.196 (Output terminal function selection) in the FR-E800 Instruction Manual (Function).
 Details of the remote register
 Remote register (from the master module to the inverter)
• Remote register description
Device No.
Signal
RWw0
Monitor code 1, 2
Signal
0: Other than forward running (during stop or reverse rotation)
1: Forward running
0: Other than reverse running (during stop or forward rotation)
1: Reverse running
*1
The function assigned to the terminal RUN is activated.
*2
SU signal
*2
OL signal
*4
The function assigned to Pr.193 is activated.
Functions assigned to terminals FU, A, B, and C are activated.
*1
*4
The function assigned to Pr.194 is activated.
*3
*3
Functions assigned to Pr.313 to Pr.315 are activated.
*3
After "1" is set in the monitor command (RYC), and the monitored value is set
in the remote register Rwr0, 1, 4 to 7, "1" is set for this signal. When "0" is set
in the monitor command (RYC), "0" is set for this signal.
After "1" is set in the frequency setting command / torque command (RYD),
and the frequency setting / torque command is written to the RAM of the
inverter, "1" is set for this signal. When "0" is set in the frequency setting
command / torque command (RYD), "0" is set for this signal.
After "1" is set in the frequency setting command / torque command (RYE),
and the frequency setting / torque command is written to the RAM and
EEPROM of the inverter, "1" is set for this signal. When "0" is set in the
frequency setting command / torque command (RYE), "0" is set for this signal.
After "1" is set in the instruction code execution request (RYF) and the
processes corresponding to the instruction codes (RWw2, 10, 12, 14, 16 and
18) are executed, "1" is set for this signal. When "0" is set in the instruction
code execution request (RYF), "0" is set for this signal.
*4
Functions assigned to Pr.195 and Pr.196 are activated.
*4
When an inverter error occurs (protective function is activated), "1" is set for
this signal.
When the inverter is ready for communication upon completion of initial setting
after power-ON or a hardware reset, "1" is set for this signal. When an inverter
error occurs (protective function is activated), "0" is set for this signal.
Set the monitor code to be monitored (refer to
specified monitor items will be stored in RWr0/RWr1.
Description
Description
page
50). When "1" is set in RYC, data of
2. Ethernet Communication
2.6 CC-Link IE Field Network Basic
1
2
3
4
5
6
7
8
9
10
45