Cc-Link Ie Tsn Configuration - Mitsubishi Electric 800 Series Instruction Manual

Communication
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

2.5.2

CC-Link IE TSN configuration

 Procedure
The following shows the procedure to connect the inverter with a Mitsubishi Electric master device.
 Before communication
1.
Connect each unit with an Ethernet cable. (Refer to
2.
Enter the IP address (Pr.1434 to Pr.1437). (Refer to
3.
Reset the inverter, or turn OFF and then ON the power.
 Registering a profile
1.
Start GX Works3.
2.
On the menu bar, select [Tool] > [Profile Management] > [Register...].
3.
Select a CSP+ file to be registered on the "Register Profile" screen, and click the [Register] button.
NOTE
• A profile is a compressed file (such as *.zip, *.ipar, and *.cspp). Register a profile without decompressing the file.
• Profile registration is not required for the next time onwards.
 Creating a project file
1.
For information on creating and opening a project, go to [Help] > [GX Works3 Help].
 Detecting an Inverter
Detection is not possible when the data link is not established with the master module. For details, refer to the Master Module
User's Manual.
1.
In the "Navigation" window, select [Parameter] > [Module Information] then select the module name.
2.
Select [Basic Settings] in the "Setting Item List" window.
page
13.)
page
15.)
17
2. Ethernet Communication
2.5 CC-Link IE TSN