No.
Name
7
Speed Actual
8
SpeedRef
9
Current Actual
11
Torque Actual
12
TorqueRef
15
Power Actual
17
Output Voltage
18
AccelTime
19
DecelTime
20
LowSpd Limit
21
HighSpd Limit
22
SpeedScale
23
Current Scale
24
Torque Scale
29
RefFromNet
*1
Writing is enabled only when the setting is the same as that of the inverter.
TCP/IP Interface Object (F5h)
The object groups TCP/IP-related settings.
Service
Class
Get_Attribute_Single
Class attribute
No.
Name
1
Revision
Access
Get
INT
Set
INT
Get
INT
Get
INT
Set
INT
Get
INT
Get
INT
Set
UINT
Set
UINT
Set
UINT
Set
UINT
Set
SINT
Set
SINT
Set
SINT
Get
BOOL
Instance
Get_Attribute_All
Get_Attribute_Single
Set_Attribute_Single
Access
Get
UINT
Type
Actual drive speed
SpeedScale
Unit: rpm / 2
Speed setting value
SpeedScale
Unit: rpm / 2
Select whether or not to use a sign for the frequency command
value using Pr.541.
Motor phase current
CurrentScale
Unit: 100mA / 2
Actual torque
TorqueScale
Unit: N·m / 2
Torque reference
TorqueScale
Unit: N·m / 2
Output power
PowerScale
Unit: W / 2
Output voltage
VoltageScale
Unit: V / 2
Acceleration time = Pr.7 (Pr.44) × Pr.18/Pr.20
Time from 0 to HighSpdLimit
Unit: ms
Deceleration time = Pr.8 (Pr.45) × Pr.18/Pr.20
Time from HighSpdLimit to 0
Unit: ms
Minimum speed limit
SpeedScale
Unit: rpm / 2
Maximum speed limit
SpeedScale
Unit: rpm / 2
Speed scaling factor
Current scaling factor
Torque scaling factor
Speed/torque command source monitoring
0: Local reference
1: Network reference
Type
0004h (Revision of the object)
Description
Description
2. Ethernet Communication
2.11 EtherNet/IP
1
2
3
4
5
6
7
8
9
10
109