Mitsubishi Electric 800 Series Instruction Manual page 70

Communication
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Pr.
Name
1449
Ethernet command source
*1
selection IP address 1
N670
1450
Ethernet command source
*1
selection IP address 2
N671
1451
Ethernet command source
*1
selection IP address 3
N672
1452
Ethernet command source
*1
selection IP address 4
N673
Ethernet command source
1453
selection IP address 3 range
*1
N674
specification
Ethernet command source
1454
selection IP address 4 range
*1
N675
specification
*1
The setting is applied after an inverter reset or next power-ON.
*2
The setting is available for the FR-E800-EPA.
*3
The setting is available for the FR-E800-EPB.
NOTE
• The monitor items and parameter settings can be read during communication with the Pr.1432 Ethernet communication
check time interval = "0 (initial value)" setting, but such operation will become faulty once the operation mode is changed to
the NET operation mode. When the NET operation mode is selected as the start-up operation mode, communication is
performed once, then an Ethernet communication fault (E.EHR) occurs.
To perform operation or parameter writing via communication, set Pr.1432 to "9999" or a value larger than the communication
cycle or retry time setting. (Refer to
 Ethernet function selection (Pr.1427 to Pr.1430)
To select BACnet/IP for the application, set "47808" in any of Pr.1427 to Pr.1430 Ethernet function selection 1 to 4.
NOTE
• Change the setting if selected communication protocols cannot be used together. (Refer to
 Ethernet IP address for command source selection (Pr.1449 to Pr.1454)
• To limit the network devices that send the operation or speed command through the Ethernet network, set the range of IP
addresses of the devices.
• When Pr.1449 to Pr.1452 = "0 (initial value)", no IP address is specified for command source selection via Ethernet. In this
case, operation commands cannot be sent via Ethernet.
Initial
Setting range
value
0
0
0 to 255
0
0
9999
0 to 255, 9999
9999
page
70.)
Setting range
To limit the network devices that send the operation or
speed command through the Ethernet network, set the
range of IP addresses of the devices.
When Pr.1449 to Pr.1452 = "0 (initial value)", no IP address
is specified for command source selection via Ethernet. In
this case, operation commands cannot be sent via Ethernet
with MODBUS/TCP protocol.
page 5
2. Ethernet Communication
1
2
3
4
5
6
7
8
9
and
page
122.)
10
69
2.8 BACnet/IP

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800

Table of Contents