Mitsubishi Electric 800 Series Instruction Manual page 101

Communication
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

To make communication between other devices and the inverter, perform the initial settings of the inverter parameters to match
the communication specifications of the devices. Data communication cannot be made if the initial settings are not made or if
there is any setting error.
Pr.
1427
Ethernet function selection 1
*1
N630
1428
Ethernet function selection 2
*1
N631
1429
Ethernet function selection 3
*1
N632
1430
Ethernet function selection 4
*1
N633
1432
Ethernet communication
N644
check time interval
1449
Ethernet command source
*1
selection IP address 1
N670
1450
Ethernet command source
*1
selection IP address 2
N671
1451
Ethernet command source
*1
selection IP address 3
N672
1452
Ethernet command source
*1
selection IP address 4
N673
Ethernet command source
1453
selection IP address 3 range
*1
N674
specification
Ethernet command source
1454
selection IP address 4 range
*1
N675
specification
*1
The setting is applied after an inverter reset or next power-ON.
*2
The setting is available for the FR-E800-EPA.
*3
The setting is available for the FR-E800-EPB.
NOTE
• The monitor items and parameter settings can be read during communication with the Pr.1432 Ethernet communication
check time interval = "0 (initial value)" setting, but such operation will become faulty once the operation mode is changed to
the NET operation mode. When the NET operation mode is selected as the start-up operation mode, communication is
performed once, then an Ethernet communication fault (E.EHR) occurs.
• To perform operation or parameter writing via communication, set Pr.1432 to "9999" or a value larger than the communication
cycle or retry time setting. (Refer to
 Ethernet function selection (Pr.1427 to Pr.1430)
To select EtherNet/IP for the application, set "44818" in any of Pr.1427 to Pr.1430 Ethernet function selection 1 to 4.
NOTE
• Change the setting if selected communication protocols cannot be used together. (Refer to
 Ethernet IP address for command source selection (Pr.1449 to Pr.1454)
• To limit the network devices that send the operation or speed command through the Ethernet network, set the range of IP
addresses of the devices.
100
2. Ethernet Communication
2.11 EtherNet/IP
Initial
Name
value
5001
45237
45238
9999
1.5 s
0
0
0
0
9999
9999
page
Setting range
502, 5000 to 5002,
5006 to 5008, 5010 to
*3
5013, 9999, 34962
,
Set the application, protocol, etc.
*2
44818
, 45237,
*2
45238, 47808
,
61450
Ethernet communication is available, but the inverter output
0
is shut off in the NET operation mode.
Set the interval of the communication check (signal loss
detection) time for all devices with IP addresses in the range
specified for Ethernet command source selection (Pr.1449
0.1 to 999.8 s
to Pr.1454).
If a no-communication state persists for longer than the
permissible time, the inverter output will be shut off.
9999
No communication check (signal loss detection)
0 to 255
To limit the network devices that send the operation or
speed command through the Ethernet network, set the
range of IP addresses of the devices.
When Pr.1449 to Pr.1452 = "0 (initial value)", no IP address
is specified for command source selection via Ethernet. In
this case, operation commands cannot be sent via Ethernet.
0 to 255, 9999
101.)
Description
page 5
and
page
122.)