Mitsubishi Electric 800 Series Instruction Manual page 86

Communication
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Pr.
Name
1442
Ethernet IP filter address 1
*1
N660
1443
Ethernet IP filter address 2
*1
N661
1444
Ethernet IP filter address 3
*1
N662
1445
Ethernet IP filter address 4
*1
N663
1446
Ethernet IP filter address 2
*1
range specification
N664
1447
Ethernet IP filter address 3
*1
range specification
N665
1448
Ethernet IP filter address 4
*1
range specification
N666
*1
The setting is applied after an inverter reset or next power-ON.
 Communication speed and full-duplex/half-duplex selection (Pr.1426)
Use Pr.1426 Link speed and duplex mode selection to set the communication speed and the full-duplex or half-duplex
system. If the operation is not performed properly in the initial setting (Pr.1426 = "0"), set Pr.1426 according to the
specifications of the connected device.
Communication
Pr.1426 setting
speed
Automatic
0 (initial value)
negotiation
1
100 Mbps
2
100 Mbps
3
10 Mbps
4
10 Mbps
 Ethernet IP filtering function (Pr.1442 to Pr.1448)
• Set the IP address range for connectable network devices (Pr.1442 to Pr.1448) to limit the connectable devices. The
setting range for IP address of connectable network devices depends on the settings in Pr.1443 and Pr.1446, Pr.1444 and
Pr.1447, and Pr.1445 and Pr.1448. (Either of the settings can be larger than the other in Pr.1443 and Pr.1446, Pr.1444
and Pr.1447, and Pr.1445 and Pr.1448.)
[Setting example 1]
Ethernet IP address for filtering
Filtering range setting
for the Ethernet IP address
In this case, the IP address range in which Ethernet communication is permitted is "192.168.x (1 to 3).xxx (100 to 150)".
[Setting example 2]
Ethernet IP address for filtering
Filtering range setting
for the Ethernet IP address
In this case, the IP address range in which Ethernet communication is permitted is "192.168.2.xxx (50 to 100)".
• When Pr.1442 to Pr.1445 = "0 (initial value)", the function is invalid.
Initial
Setting range
value
0
0
0 to 255
0
0
9999
9999
0 to 255, 9999
9999
Full-duplex/half-
duplex system
The communication speed and the communication mode (half-duplex/full-
Automatic
duplex) are automatically negotiated to ensure the optimum setting. To set
negotiation
automatic negotiation, auto negotiation setting is required also in the master
station.
Full duplex
Half duplex
Full duplex
Half duplex
Pr.1442
Pr.1443
192
168
The range is between
the values set in both
parameters.
Pr.1446
9999
Pr.1442
Pr.1443
192
168
The range is between
the values set in both
parameters.
Pr.1446
9999
Setting range
Set the range of connectable IP addresses for the network devices.
(When Pr.1442 to Pr.1445 = "0 (initial value)", the function is
invalid.)
Remarks
Pr.1444
Pr.1445
1
100
The range is between
the values set in both
parameters.
Pr.1447
Pr.1448
3
150
Pr.1444
Pr.1445
2
100
Pr.1447
Pr.1448
9999
50
85
2. Ethernet Communication
2.10 SLMP
1
2
3
4
5
6
7
8
9
10

Advertisement