Mitsubishi Electric 800 Series Instruction Manual page 98

Communication
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Item
Subcommand
Number of devices for bit access
Number of devices for word
access
Number of devices for double-
word access
Word access
Double-word access
Device No.
Device code
Set/reset
• Response data
None
• Remote Run
Remote Run is performed to the inverter.
• Request data
Clear
Mode
mode
H01 H10 H00 H00
Item
Forced execution of the remote RUN is not
allowed.
Mode
Forced execution of the remote RUN is allowed.
Devices are not cleared (initialized).
Clear mode
Devices are cleared.
• Response data
None
• Remote Stop
Remote Stop is performed to the inverter.
• Request data
H02 H10 H00 H00 H01 H00
• Response data
None
• Read Type Name
The model name and model code of the inverter are read.
• Request data
H01 H01 H00 H00
• Response data
Item
The inverter model is stored. Up to 16 characters can be stored. If the model name is shorter than 16 characters,
Model
a space (H20) is stored instead of a character.
(Example) FR-E800-E inverter: FR-E800-E
Model code
Fixed to H054F
Specify the unit (bit/word) for writing.
Specify the number of target devices.
Specify the devices according to the number set in the request data for word access. It is not necessary to
specify the devices when "0" is set.
Specify the devices according to the number set in the request data for double word access. It is not
necessary to specify the devices when "0" is set.
Specify the device number of target devices. (Refer to
Specify the type of the target devices. (Refer to
Specify ON/OFF of the bit devices.
• ON: H01
• OFF: H00
H00
Description
Model
Description
page
93.)
page
90.)
H0100
H0300
H00
H01, H02
Model
code
Description
97
2. Ethernet Communication
2.10 SLMP
1
2
3
4
5
6
7
8
9
10

Advertisement