Mitsubishi Electric 800 Series Instruction Manual page 128

Communication
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Commercially available products (as of December 2019)
Product name
RS-485 distributor
 Terminating resistor
Prepare a 100 Ω 1/2 W terminating resistor such as the following.
1
0
1
=100Ω
(10¹)
• Connect the terminating resistor between pin No. 3 (RDA) and pin No. 6 (RDB).
• Connect the terminating resistor to only the inverter remotest from the programmable controller.
Model
BMJ-8-28N (Pins No. 2 and No. 8 are not
connected internally.)
(A plug with a terminating resistor is not used.)
DMDH-3PN
DMDH-10PN
Manufacturer
HACHIKO ELECTRIC CO., LTD.
Diatrend Corp.
3. RS-485 Communication
1
2
3
4
5
6
7
8
9
10
127
3.2 Wiring

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800

Table of Contents