Mitsubishi Electric 800 Series Instruction Manual page 153

Communication
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

• Fault history
Register
40501
Fault record 1
40502
Fault record 2
40503
Fault record 3
40504
Fault record 4
40505
Fault record 5
40506
Fault record 6
40507
Fault record 7
40508
Fault record 8
40509
Fault record 9
40510
Fault record 10
• Product profile
Register
44001
Model (1st and 2nd characters)
44002
Model (3rd and 4th characters)
44003
Model (5th and 6th characters)
44004
Model (7th and 8th characters)
44005
Model (9th and 10th characters)
44006
Model (11th and 12th characters)
44007
Model (13th and 14th characters)
44008
Model (15th and 16th characters)
44009
Model (17th and 18th characters)
44010
Model (19th and 20th characters)
44011
Capacity (1st and 2nd characters) Read
44012
Capacity (3rd and 4th characters)
44013
Capacity (5th and 6th characters)
NOTE
• When a 32-bit parameter setting or monitor item is read and the value to be read exceeds HFFFF, HFFFF is returned.
 Pr.343 Communication error count
• The communication error occurrence count can be checked.
Parameter
343
NOTE
• The communication error count is temporarily stored in the RAM memory. The value is not stored in the EEPROM, and so is
cleared to 0 when power is reset and the inverter is reset.
152
3. RS-485 Communication
3.5 MODBUS RTU
Definition
Read/write
Read/write
Read
Read
Read
Read
Read
Read
Read
Read
Read
Definition
Read/write
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Setting range
(Read-only)
Remarks
Being 2 bytes in length, the data is stored as H00○○.
Refer to the lowest 1 byte for the error code. (For details on error codes,
refer to the FR-E800 Instruction Manual (Maintenance).)
The fault history is batch-cleared by writing to register 40501.
Set any value as data.
Remarks
The inverter model can be read in ASCII code.
"H20" (blank code) is set for blank area.
Example) FR-E820-1:
H46, H52, H2D, H45, H38, H32, H30, H2D, H31, H20......H20
The capacity in the inverter model can be read in ASCII code.
Data is read in increments of 0.1 kW, and rounds down to 0.01 kW
increments.
"H20" (blank code) is set for blank area.
Example) 0.75K: "
7" (H20, H20, H20, H20, H20, H37)
Minimum setting range
1
Initial value
0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800

Table of Contents