connecting them with the inverter.
 Do not connect the braking resistor with other terminals except for PB and (-). Damage to
the inverter or braking circuit or fire may occur.
 Connect the braking device with the inverter according to the diagram. Incorrect wiring may
cause damage to the inverter or other devices.
Model
100% of the
XKL-040-21
XKL-075-21
XKL-150-21
XKL-220-21
XKL-075-43
XKL-150-43
XKL-220-43
Note:
Select a resistor with wattage and resistance rating as specified in the table above.
The braking resistor may increase the braking torque of the inverter. Above table is measured at 100% braking
torque, 10%, 50% and 80% braking usage rate, the user can select braking level according to duty cycle.
 Do not use brake resistor with a resistance below the minimum value specified for the particular
drive. The drive and the internal chopper are not able to handle the overcurrent caused by the
low resistance.
 Increase the power of the braking resistor properly in accordance of the duty cycle (the duty
cycle is more than 10%).
C.7.2 Connection of external brake resistor
Install all resistors in a place where they have air clearance.
 The materials near the brake resistor must be non-flammable. The surface temperature of the
resistor can be extremely high, ensure sufficient ventilation for heat dissipation.
Only external braking resistor is needed in IMO XKL.
Dissipation
Braking
power (kW)
resistor at
braking
10% braking
torque(Ω)
361
0.06
192
0.11
96
0.23
65
0.33
653
0.11
326
0.23
222
0.33
Appendix C Peripherial options and parts
Dissipation
power (kW)
50% braking
0.30
0.56
1.1
1.7
0.6
1.1
1.7
+
PB
91
Dissipation
power (kW)
Min braking
resistor (Ω)
80% braking
0.48
42
0.90
42
1.8
30
2.6
21
0.9
100
1.8
100
2.6
54