Detailed instruction of parameters
Selects the run command method of the inverter.
The control command of the inverter includes: start,
stop, forward, reverse, jogging and fault reset.
0:Keypad run command method ("LOCAL/REMOT" light
off)
Run command control by RUN, STOP/RST on the
keypad.
Set the multi-function key QUICK/JOG to FWD/REV
shifting function (P07.02=3) to change the running
direction; press RUN and STOP/RST simultaneously in
running state to make the inverter coast to stop.
1:Terminal run command method ("LOCAL/REMOT"
flashing)
Terminal run command control by the forward rotation,
reverse rotation and forward jogging and reverse jogging
of the multi-function terminals
2:Communication
run
("LOCAL/REMOT" on);
The
running
command
communication
Sets the maximum output frequency of the drive.
Acceleration and deceleration times are based on this
setting.
Setting range: P00.04~400.00Hz
Limits the maximum running frequency.
Setting range:P00.05~P00.03 (Max. output frequency)
Limits the minimum running frequency.
The inverter runs at the lower limit frequency even if the
set frequency is lower than the low limit setting.
Note: Max. Output frequency ≥ Frequency high limit ≥
Frequency low limit.
Setting range:0Hz~P00.04 (Frequency high limit.).
0:Keypad data setting.
Modify the value of function code P00.10 (set the
frequency by keypad) to modify the frequency by the
keypad.
1:Analog AI1 setting
23
command
method
is
controlled
by
via
Function Parameters
Default
Modify
value
0
50.00Hz
50.00Hz
0.00Hz
0
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents