IMO iDrive2 XKL Instruction Manual page 33

General application inverter
Table of Contents

Advertisement

iDrive2 inverters
Function
Name
code
Motor V/F
P04.03
frequency
point 1
Motor V/F
P04.04
voltage
point 1
Motor V/F
P04.05
frequency
point 2
Motor V/F
P04.06
voltage point
2
Motor V/F
P04.07
frequency
point 3
Motor V/F
P04.08
voltage point
3
Detailed instruction of parameters
and the current of the inverter will increase the
temperature of the inverter and decrease the efficiency.
When the torque boost is set to 0.0%, the inverter is
automatic torque boost.
Torque boost threshold: below this frequency point, the
torque boost is valid, but over this frequency point, the
torque boost is invalid.
The setting range of P04.01: 0.0%: (automatic)
0.1%~10.0%
The setting range of P04.02:0.0%~50.0%
When P04.00 =1, the user can set V//F curve through
P04.03~P04.08.
V/F is generally set according to the load of the motor.
Note: V1 < V2 < V3,f1 < f2 < f3. Too high or low
frequency voltage can overheat the motor excessively or
cause damage to the inverter.
The setting range of P04.03: 0.00Hz~P04.05
The setting range of P04.04, P04.06 and P04.08 :
0.0%~110.0%
The setting range of P04.05:P04.03~ P04.07
The setting range of P04.07:P04.05~P02.02 (the rated
frequency of motor 1)
33
Function Parameters
Default
Modify
value
0.00Hz
00.0%
00.00Hz
00.0%
00.00Hz
00.0%