IMO iDrive2 XKL Instruction Manual page 27

General application inverter
Table of Contents

Advertisement

iDrive2 inverters
Function
Name
code
P01.00
Start mode
Starting
frequency of
P01.01
direct
start-up
Retention
time of the
P01.02
starting
frequency
The braking
current
P01.03
before
starting
The braking
P01.04
time before
Detailed instruction of parameters
Restoring to the default value will cancel the user
password, please use this function with caution.
P01 Group Start-up and stop control
0:Start-up directly:start from the starting frequency
P01.01
1:Start-up after DC braking: start the motor from the
starting frequency after DC braking (set the parameter
P01.03 and P01.04). It is suitable in the cases where
reverse rotation may occur to the low inertia load during
starting.
Starting frequency of direct start-up means the original
frequency during the inverter starting. See P01.02 for
detailed information.
Setting range: 0.00~50.00Hz
Set a proper starting frequency to increase the torque of
the inverter during starting. During the retention time of
the starting frequency, the output frequency of the
inverter is the starting frequency. And then, the inverter
will run from the starting frequency to the set frequency.
If the set frequency is lower than the starting frequency,
the inverter will stop running and keep in the stand-by
state. The starting frequency is not limited in the lower
limit frequency.
Setting range: 0.0~50.0s
The inverter will carry out DC braking at the braking
current set before starting and it will speed up after the
DC braking time. If the DC braking time is set to 0, the
DC braking is invalid.
The stronger the braking current, the bigger the braking
power. The DC braking current before starting means
27
Function Parameters
Default
Modify
value
0
0.50Hz
0.0s
0.0%
0.00s

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents