iDrive2 inverters
Function
Name
code
Output
terminal
P11.13
action
selection
during fault
Local
P14.00
communicati
on address
P14.01
Baud rate
Digital bit
P14.02
checkout
setting
Detailed instruction of parameters
Select the action of fault output terminals on
undervoltage and fault reset.
0x00~0x11
LED ones:
0:Action under fault undervoltage
1:No action under fault undervoltage
LED tens:
0:Action during the automatic reset
1:No action during the automatic reset
P14 Group Serial communication
The setting range:1~247
When the master is writing the frame, the
communication address of the slave is set to 0; the
broadcast address is the communication address. All
slaves on the MODBUS fieldbus can receive the frame,
but the slave doesn't answer.
The communication address of the drive is unique in the
communication net. This is the fundamental for the point
to point communication between the upper monitor and
the drive.
Note: The address of the slave cannot be set to 0.
Set the digital transmission speed between the upper
monitor and the inverter.
0:1200BPS
1:2400BPS
2:4800BPS
3:9600BPS
4:19200BPS
5:38400BPS
Note: The baud rate between the upper monitor and the
inverter must be the same. The higher the baud rate, the
faster the communication speed.
The data format between the upper monitor and the
inverter must be the same.
0: No check (N,8,1) for RTU
1:Odd check (E,8,1) for RTU
2:Even check (O,8,1) for RTU
3:No check (N,8,2) for RTU
61
Function Parameters
Default
Modify
value
0x00
1
4
1