iDrive2 inverters
Function
Name
code
Communicati
P14.03
on response
delay
Communicati
P14.04
on overtime
fault time
Transmission
P14.05
fault
processing
Communicati
on
P14.06
processing
action
selection
Detailed instruction of parameters
4: Odd check (E,8,2) for RTU
5:Even check(O,8,2) for RTU
0~200ms
It means the interval time between the in time the drive
receives the data and sends it to the upper monitor. If the
answer delay is shorter than the system processing time,
then the answer delay time is the system processing
time, if the answer delay is longer than the system
processing time, then after the system deal with the
data, waits until achieving the answer delay time to send
the data to the upper monitor.
0.0 (invalid),0.1~60.0s
When the function code is set as 0.0, the communication
overtime parameter is invalid.
When the function code is set as non-zero, if the interval
time between two communications exceeds the
communication overtime, the system will report "485
communication faults" (CE).
Generally, set it as invalid; set the parameter in the
continuous communication to monitor the
communication state.
0:Alarm and stop freely
1:No alarm and continue to run
2:No alarm and stop according to the stop means (only
under the communication control)
3:No alarm and stop according to the stop means (under
all control modes)
0x00~0x11
LED ones:
0: Operation with response: the drive will respond to all
reading and writing commands of the upper monitor.
1: Operation without response;The drive only responds
to the reading command other than the writing command
of the drive. The communication efficiency can be
increased by this method.
LED tens:(reserved)
62
Function Parameters
Default
Modify
value
5
0.0s
0
0x00